Air Does Not Come Out, Or Airflow Capacity Is Insufficient
Trouble symptom:
- Airflow capacity is insufficient.
- Air does not come out when operating the fan dial.
Trouble causes:
- Airflow capacity failure
- CAN communication failure
- A/C control panel failure
- Blower motor failure
Wiring diagram:
Air conditioning system Ref. to WIRING SYSTEM>Air Conditioning System>WIRING DIAGRAM .
- CHECK A/C CONTROL PANEL.
- Using Subaru Select Monitor, check the following data of the data monitor. Ref. to AIR CONDITIONER(DIAGNOSTICS)>Data Monitor .
- Air mix door actuator position (driver's side)
- Air mix door actuator position (passenger's side)
- Blower Fan Level
- Turn the temperature control dial at MAX COOL and increase and decrease the A/C control panel fan dial. (For vehicles with left/right independent air conditioner, perform setting on both sides.)
Do [Air mix door actuator position (driver's side)] and Air mix door actuator position (passenger's side) indicate "0%"? Also, does [Blower Fan Level] increase or decrease in accordance with the fan dial operation?
- Yes : Go to 2.
- No : Go to 5 .
- Using Subaru Select Monitor, check the following data of the data monitor. Ref. to AIR CONDITIONER(DIAGNOSTICS)>Data Monitor .
- CHECK AIRFLOW CAPACITY.
Turn the temperature control dial to LO (both dials for the models equipped with left/right independent air conditioning function), A/C control panel fan dial to MAX and FRESH/RECIRC switch to RECIRC.
Is the airflow capacity insufficient for the same model?
- Yes : Go to 3.
- No : The circuit has returned to a normal condition at this time. Reproduce the failure, and then perform the diagnosis.
NOTE: In this case, temporary poor contact of connector, temporary open or short circuit of harness may be the cause. - CHECK A/C FILTER.
Check the A/C filter.
Is the check result OK?
- Yes : Go to 4.
- No : Clean or replace the A/C filter.
- CHECK EACH DUCT.
Check each duct joint for disconnection or clogging.
Is the check result OK?
- Yes : Go to 5.
- No : Repair the faulty duct.
- CHECK A/C CONTROL PANEL.
- Turn the ignition switch to ON.
- Turn the fan dial to the maximum position.
- Using Subaru Select Monitor, check [Blower Fan Level] of the data monitor. Ref. to AIR CONDITIONER(DIAGNOSTICS)>Data Monitor .
Does [Blower Fan Level] indicate "7"?
- Yes : Go to 6.
- No : Replace the A/C control panel. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Control Panel>REMOVAL .
- CHECK A/C CONTROL PANEL.
- Turn the fan dial to the minimum position.
- Using Subaru Select Monitor, check [Blower Fan Level] of the data monitor.
Does [Blower Fan Level] indicate "1"?
- Yes : Go to 7.
- No : Replace the A/C control panel. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Control Panel>REMOVAL .
- CHECK CONNECTOR.
Check for poor contact of connector.
Is the check result OK?
- Yes : Go to 8.
- No : Repair the connector.
- CHECK FUSE.
- Remove a fuse in the fuse & relay box.
- Check the condition of fuse.
Is the check result OK?
- Yes : Go to 9.
- No : Replace the fuse.
- CHECK BLOWER MOTOR RELAY ON SIGNAL.
- Stop the engine.
- Turn the fan dial OFF.
- Turn the ignition switch to ON.
- Using a tester, measure the voltage between the A/C control panel connector (i88) and chassis ground.
Connector & terminal
(i88) No. 9 (+) - Chassis ground (-):
Is the voltage 10 V or more?
- Yes : Go to 10.
- No :
- Check for open or short circuit in the harness between fuse and ECM.
- Check the blower relay connector and relay unit. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Relay and Fuse>INSPECTION>CHECK RELAY .
- CHECK BLOWER MOTOR RELAY ON SIGNAL.
- Start the engine.
- Turn the fan dial to ON.
- Using a tester, measure the voltage between the A/C control panel connector (i88) and chassis ground.
Connector & terminal
(i88) No. 9 (+) - Chassis ground (-):
Is the voltage 0 V?
- Yes : Go to 11.
- No : Replace the A/C control panel. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Control Panel>REMOVAL .
- CHECK BLOWER MOTOR POWER SUPPLY CIRCUIT.
- Turn the ignition switch to ON.
- Turn the fan dial to ON.
- Use a tester to measure the voltage between the blower motor connector (B87) and chassis ground.
Connector & terminal
(B87) No. 2 (+) - Chassis ground (-):
Is the voltage 10 V or more?
- Yes : Go to 12.
- No
:
- Check the blower motor power supply line harness for open circuit or connector disconnection.
- Check the blower relay connector and relay unit. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Relay and Fuse>INSPECTION>CHECK RELAY .
- CHECK BLOWER MOTOR UNIT.
Check the blower motor. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Blower Motor>INSPECTION .
Is the check result OK?
- Yes : Go to 13.
- No : Replace the blower motor. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Blower Motor>REMOVAL .
- CHECK HARNESS (OPEN CIRCUIT).
- Disconnect the power transistor and A/C control panel connector.
- Using a tester, measure the resistance between harness terminals.
Connector & terminal
(B386) No. 4 - (B57) No. 4:
(B87) No. 1 - (B57) No. 3:
(B57) No. 2 - (i88) No. 40:
(B57) No. 1 - Chassis ground:
Is the resistance less than 1 Ω?
- Yes : Go to 14.
- No : Repair or replace the open circuit of harness.
- CHECK HARNESS (GROUND SHORT CIRCUIT).
Use a tester to measure the harness resistance between the power transistor connector and chassis ground.
Connector & terminal
(B57) No. 2 - Chassis ground:
Is the resistance less than 1 Ω?
- Yes : Repair or replace the short circuit of the harness.
- No : Go to 15.
- CHECK POWER TRANSISTOR.
Replace the power transistor with a properly functioning part.
Does the blower motor rotate?
- Yes : Replace the power transistor. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Power Transistor (Auto A/C Model)>REMOVAL .
- No : Replace the A/C control panel. Ref. to HVAC SYSTEM (HEATER, VENTILATOR AND A/C)>Control Panel>REMOVAL .