DTC B1231 or DTC indicator 4: An Open in the Evaporator Temperature Sensor Circuit

  1. Clear the DTCs with the HDS.
  2. Turn the ignition switch to LOCK (0), and then back to ON (II).
  3. Do the Self-Diagnostic Function with the HDS (see HOW TO USE THE SELF-DIAGNOSTIC FUNCTION WITH THE HDS  ) or the HVAC control unit (see HOW TO USE THE HVAC CONTROL UNIT SELF-DIAGNOSTIC FUNCTION WITHOUT THE HDS  ).
  4. Check for DTCs.

    Is DTC B1231 or 4 indicated? 

    YES  -Go to step 5.

    NO  -Intermittent failure. Check for loose wires or poor connections on the evaporator temperature sensor circuit.

  5. Turn the ignition switch to LOCK (0).
  6. Remove the evaporator temperature sensor (see EVAPORATOR TEMPERATURE SENSOR REPLACEMENT  ), and test it (see EVAPORATOR TEMPERATURE SENSOR TEST  ).

    Is the evaporator temperature sensor OK? 

    YES  -With the evaporator temperature sensor disconnected, go to step 7.

    NO  -Replace the evaporator temperature sensor (see EVAPORATOR TEMPERATURE SENSOR REPLACEMENT  ).

  7. Disconnect the HVAC control unit 28P connector.
  8. Check for continuity between HVAC control unit 28P connector terminal No. 22 and evaporator temperature sensor 2P connector terminal No. 2.
    Fig 1: Checking Continuity Between HVAC Control Unit 28P Connector Terminal No. 22 And Evaporator Temperature Sensor 2P Connector Terminal No. 2
    G06968113Courtesy of AMERICAN HONDA MOTOR CO., INC.

    Is there continuity? 

    YES  -Go to step 9.

    NO  -Repair an open in the wire between the HVAC control unit and the evaporator temperature sensor.

  9. Check for continuity between HVAC control unit 28P connector terminal No. 13 and evaporator temperature sensor 2P connector terminal No. 1.
    Fig 2: Checking Continuity Between HVAC Control Unit 28P Connector Terminal No. 13 And Evaporator Temperature Sensor 2P Connector Terminal No. 1
    G06968114Courtesy of AMERICAN HONDA MOTOR CO., INC.

    Is there continuity? 

    YES  -Check for loose wires or poor connections at the HVAC control unit 28P connector and at the evaporator temperature sensor 2P connector. If the connections are good, substitute a known-good HVAC control unit, and recheck. If the symptom/indication goes away, replace the original HVAC control unit (see HVAC CONTROL UNIT REMOVAL/INSTALLATION  ).

    NO  -Repair an open in the wire between the HVAC control unit and the evaporator temperature sensor.