Test Description
WARNING: This page is about a different car, the 2007 Saturn Vue. However, it is still accessible from the selected car via links, so may be relevant.
The numbers below refer to the step numbers on the diagnostic table.
- 2: The air conditioning (A/C) compressor relay output is disabled if the engine coolant temperature is above 96°C (205°F).
- 3: Place the mode switch in any position except OFF, and place the air temperature control switch in a cold setting. Use the bi-level mode for consistent testing of the A/C system operation.
- 6: The HVAC control module is inoperative if the module does not respond to any operator control requests.
- 23: The compressor is disabled when the evaporator temperature goes below 3°C (38°F).
- 34: Check the connection by removing and securely reinstalling before replacement of the HVAC control is considered.
HVAC Compressor Clutch Does Not Engage (Hybrid)
| Step | Action | Yes | No |
|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: The air conditioning (A/C) compressor clutch will not engage if an A/C request has been made, and a powertrain DTC has not been set. |
|||
| 1 | Did you perform the Vehicle Diagnostic System Check - Vehicle? | Go to Step 2 | Go to Diagnostic System Check - Vehicle |
| 2 |
|
Go to Engine Overheating | Go to Step 3 |
| 3 |
IMPORTANT:
For A/C compressor operation, the evaporator air temperature must be above 3°C (38°F).
|
Go to Testing for Intermittent Conditions and Poor Connections | Go to Step 4 |
| 4 |
|
Go to Step 5 | Go to Leak Testing |
| 5 |
|
Go to Step 6 | Go to Step 24 |
| 6 | Is the HVAC control module inoperative? | Go to Step 16 | Go to Step 7 |
| 7 |
|
Go to Step 10 | Go to Step 8 |
| 8 |
|
Go to Step 9 | Go to Step 18 |
| 9 |
|
Go to Step 43 | Go to Step 10 |
| 10 | With a scan tool, command the A/C compressor relay ON and OFF. Does the A/C compressor relay turn ON and OFF with each command? |
Go to Step 14 | Go to Step 11 |
| 11 |
|
Go to Step 12 | Go to Step 27 |
| 12 |
|
Go to Step 29 | Go to Step 13 |
| 13 | Does the test lamp remain illuminated with each command? | Go to Step 21 | Go to Step 19 |
| 14 |
|
Go to Step 15 | Go to Step 26 |
| 15 |
|
Go to Step 29 | Go to Step 22 |
| 16 | Test the ignition 3 voltage circuit of the HVAC control module for the following:
Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? |
Go to Step 43 | Go to Step 17 |
| 17 | Test the ground circuit of the HVAC control module for an open. Refer to Circuit Testing
and Wiring Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 34 |
| 18 |
|
Go to Step 31 | Go to Step 20 |
| 19 | Test the control circuit of the A/C compressor relay for an open. Refer to Circuit Testing
and Wiring Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 35 |
| 20 | Test the A/C request signal circuit for the following:
Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? |
Go to Step 43 | Go to Step 23 |
| 21 | Test the control circuit of the A/C compressor relay for a short to ground. Refer to Circuit Testing
and Wiring Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 35 |
| 22 | Test the supply voltage circuit at the A/C compressor relay for the following:
Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? |
Go to Step 43 | Go to Step 25 |
| 23 | View the evaporator voltage in the BCM scan tool data list under A/C sensor. Refer to Air Temperature Description and Operation for the evaporator sensor temperature to voltage conversion chart. Is the Evaporator Voltage parameter greater than the voltage range of 2.45 V-2.55 V which equals a temperature range of 36-38°F? |
Go to Step 24 | Go to Step 32 |
| 24 | Test the ground circuit of the A/C refrigerant pressure sensor for a high resistance or for an open. Refer to Circuit Testing
and Wiring Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 28 |
| 25 | Test the ground circuit of the A/C compressor for a high resistance or for an open. Refer to Circuit Testing
and Wiring Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 30 |
| 26 | Repair the switch side voltage supply circuit of the relay. Refer to Wiring Repairs
. Did you complete the repair? |
Go to Step 43 | - |
| 27 | Repair the coil side of the voltage supply circuit of the relay. Refer to Wiring Repairs
. Did you complete the repair? |
Go to Step 43 | - |
| 28 | Inspect for poor connections at the harness connector of the A/C refrigerant pressure sensor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 36 |
| 29 | Inspect for poor connections at the relay. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 38 |
| 30 | Inspect for poor connections at the harness connector of the A/C compressor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 39 |
| 31 | Inspect for poor connections at the harness connector of the BCM. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 41 |
| 32 | Test the evaporator temperature sensor circuits for the following:
Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? |
Go to Step 43 | Go to Step 33 |
| 33 | Inspect for poor connections at the harness connector of the evaporator low temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 34 |
| 34 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 37 |
| 35 | Inspect for poor connections at the harness connector of the ECM/PCM. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
. Did you find and correct the condition? |
Go to Step 43 | Go to Step 42 |
| 36 | Replace the A/C refrigerant pressure sensor. Refer to Air Conditioning (A/C) Refrigerant Pressure Sensor Replacement (L61/L66)
or Air Conditioning (A/C) Refrigerant Pressure Sensor Replacement (LAT)
. Did you complete the replacement? |
Go to Step 43 | - |
| 37 | Replace the evaporator low temperature sensor. Refer to Air Conditioning (A/C) Refrigerant Low Temperature Sensor Replacement
. Did you complete the replacement? |
Go to Step 43 | - |
| 38 | Replace the relay. Refer to Relay Replacement (Attached to Wire Harness)
or Relay Replacement (Within an Electrical Center)
. Did you complete the replacement? |
Go to Step 43 | - |
| 39 | Replace the A/C compressor. Refer to Compressor Replacement (L61)
or Compressor Replacement (L66)
or Compressor Replacement (LAT)
. Did you complete the replacement? |
Go to Step 43 | - |
| 40 | Replace the HVAC control module. Refer to Control Module References
for replacement, setup, and programming. Did you complete the replacement? |
Go to Step 43 | - |
| 41 | Replace the BCM. Refer to Control Module References
for replacement, setup, and programming. Did you complete the replacement? |
Go to Step 43 | - |
| 42 | Replace the ECM/PCM. Refer to Control Module References
for replacement, setup, and programming. Did you complete the replacement? |
Go to Step 43 | - |
| 43 | Operate the system in order to verify the repair. Did you correct the condition? |
System OK | Go to Step 4 |