Check At A/C-Ecu Terminal
CONNECTOR TERMINAL REFERENCE
| Terminal No. | Check items | Check conditions | Normal conditions |
|---|---|---|---|
| 1 | Power transistor (DRAIN) | Air volume control dial: Maximum air volume | 0 to 2 V |
| 2 | Power transistor (GATE) | Air volume control dial: Maximum air volume | Battery voltage |
| 3 - 8 | - | - | - |
| 9 | A/C control panel (input) | - | - |
| 10 | A/C control panel (input) | - | - |
| 11, 12 | - | - | - |
| 13 | Battery power supply | Always | Battery voltage |
| 14 | Ground | Always | 1 V or less |
| 15 | IG1 power supply | Ignition switch: IG1 | Battery voltage |
| 16 | A/C pressure sensor input | Refer to SIMPLE INSPECTION OF THE A/C PRESSURE SENSOR . | Refer to SIMPLE INSPECTION OF THE A/C PRESSURE SENSOR . |
| 17 | Interior temperature sensor | Sensor probe temperature: 25°C (77°F) (4.0 kΩ) | 2.1 to 2.7 V |
| 18 | - | - | - |
| 19 | Sensor ground | Always | 1 V or less |
| 20 | A/C pressure sensor power supply | Ignition switch: IG2 | 5 V |
| 21 | Fin thermo sensor ground | Always | 1 V or less |
| 22 | Fin thermo sensor | Sensor probe temperature: 25°C (77°F) (4.0 kΩ) | 2.1 to 2.7 V |
| 23 | - | - | - |
| 24 | Motor for air outside/inside air circulation switching damper | - | - |
| 25 | Motor for air outside/inside air circulation switching damper | - | - |
| 26 | Motor for air outside/inside air circulation switching damper | - | - |
| 27 | Motor for air outside/inside air circulation switching damper | - | - |
| 28 | Air mix damper motor | - | - |
| 29 | Motor power supply | - | - |
| 30 | Air outlet changeover damper motor | - | - |
| 31 | Air outlet changeover damper motor | - | - |
| 32 | Air outlet changeover damper motor | - | - |
| 33 | Air outlet changeover damper motor | - | - |
| 34 | Air mix damper motor | - | - |
| 35 | Air mix damper motor | - | - |
| 36 | Air mix damper motor | - | - |