Check Air Conditioning System For Leakage - AR83.30-P-1761S
Model 223
| Risk of explosion when using a forming gas with incorrect mixing ratio. Risk of suffocation due to inhalation of forming gas. Risk of injury due to bursting of high-pressure hoses. | Wear safety glasses and protective gloves. No smoking or open flames. Work in well-ventilated rooms only. | AS83.00-Z-0001-02A | |
| Notice | Procedure for a damaged or leaky air conditioning system | AH83.30-P-0004-01KOA | |
| Check | |||
| 1 | Evacuate air conditioning system. | AR83.30-P-1760S | |
| 2 | Carry out preliminary check for pressure drop test. | ||
| 000 588 37 21 00 Leak tester | WS83.00-P-0067B | ||
| 3 | Fill air conditioning with forming gas and check pressure drop. | ||
| 000 588 37 21 00 Leak tester | Consistent ambient conditions must therefore be strictly ensured. |
WS83.00-P-0067B | |
| *BE83.30-P-1001-04A | |||
| 4 | Check for leakage on air conditioning system using gas detection unit. | If no pressure drop was detected. | |
| 000 588 31 21 00 Gas detection unit | If there is a problem, ↓ Replace the damaged component parts of the air conditioning system. |
WS47.00-P-0077B | |
| 5 | Release forming gas from leak tester. | ||
| 6 | Fill air conditioning. | AR83.30-P-1760S |
AIR CONDITIONING
| Number | Designation | Model 223, 294, 295, 296, 297 | ||
|---|---|---|---|---|
| BE83.30-P-1001-04A | Pressure drop in refrigerant circuit filled with test gas | Test pressure | bar | 15 |
| Test period | h | 4 | ||
| Permissible fluctuation of ambient temperature | °C | ±2 | ||
| Pressure drop | bar | 0 | ||