Check Air Conditioning System For Leakage - AR83.30-P-1761XG
Model 463
as of model year 2019
| Risk of explosion when using a forming gas with incorrect mixing ratio. Risk of suffocation due to inhalation of forming gas. Risk of injury due to bursting of high-pressure hoses. | Wear safety glasses and protective gloves. No smoking or open flames. Work in well-ventilated rooms only. | AS83.00-Z-0001-02A | |
| Procedure for a damaged or leaky air conditioning system | AH83.30-N-0004-01A | ||
| Check | |||
| 1 | Evacuate air conditioning system. | AR83.30-P-1760XG | |
| 2 | Fill air conditioning with forming gas and check pressure drop. | ||
| 000 588 19 21 00 Leak tester | Consistent ambient conditions must therefore be strictly ensured. |
WS83.00-P-0035B | |
| Pressure drop in refrigerant circuit filled with test gas | *BE83.30-P-1001-04A | ||
| 3 | Identify leakage on air conditioning system using gas detection unit. | If there is a pressure drop in the refrigerant circuit. | |
| 000 588 03 21 00 Gas detector | If a leakage is present, ↓ Replace the damaged component parts of the air conditioning system. |
WS47.00-P-0019B | |
| 4 | Release forming gas from leak tester. | ||
| 5 | Fill the air conditioning system. | AR83.30-P-1760XG |
AIR CONDITIONING
| Number | Designation | Model 463 as of model year 2019 | ||
|---|---|---|---|---|
| BE83.30-P-1001-04A | Pressure drop in refrigerant circuit filled with test gas | Test pressure | bar | 15 |
| Test period | h | 4 | ||
| Permissible fluctuation of ambient temperature | °C | ± 2 | ||
| Pressure drop | bar | 0 | ||