Check Air Conditioning System For Leakage - AR83.30-P-1761LWO
Model 238
| Risk of explosion when using a forming gas with incorrect mixing ratio. Risk of suffocation due to inhalation of forming gas. Risk of injury due to bursting of high-pressure hoses. | Wear safety glasses and protective gloves. No smoking or open flames. Work in well-ventilated rooms only. | AS83.00-Z-0001-02A | |
| Notice | Procedure for a damaged or leaky air conditioning system | AH83.30-P-0004-01KOA | |
| Check | |||
| 1 | Evacuate air conditioning system | AR83.30-P-1760LWO | |
| 2 | Fill air conditioning with forming gas and check pressure drop | ||
| 000 588 19 21 00 Leak tester | Consistent ambient conditions must therefore be strictly ensured. |
WS83.00-P-0035B | |
| Pressure drop in refrigerant circuit filled with test gas | *BE83.30-P-1001-04A | ||
| 3 | Check for leaks in air conditioning system using gas detection unit | If no pressure drop was detected. | |
| 000 588 03 21 00 Gas detector | In the event of leakage ↓ Replace damaged components of the air conditioning system. |
WS47.00-P-0019B | |
| 4 | Release forming gas from leak tester | ||
| 5 | Charge air conditioning system | AR83.30-P-1760LWO |
AIR CONDITIONING
| Number | Designation | Model 118, 164, 166, 167, 169, 171, 177, 190, 197, 199, 204, 205, 206, 207, 209, 211, 212, 216, 218, 219, 221, 230, 238, 240, 243, 245, 247, 251, 253, 257, 290, 292, 293 Model 213, 217, 222 except code 1U6 (R744 refrigerant) | ||
|---|---|---|---|---|
| BE83.30-P-1001-04A | Pressure drop in refrigerant circuit filled with test gas | Test pressure | bar | 15 |
| Test period | h | 4 | ||
| Permissible fluctuation of ambient temperature | °C | ± 2 | ||
| Pressure drop | bar | 0 | ||