Refrigerant System Evacuation
WARNING: This page is about a different car, the 2002 Mazda B4000, 2002 Mazda B3000, and 2002 Mazda B2300. However, it is still accessible from the selected car via links, so may be relevant.
NOTE:
Mazda Motor Company recommends use of an A/C service center to carry out recovery, evacuation and charging of the refrigerant system. If an A/C service center is not available, system recovery, evacuation, and charging may be accomplished using a separate vacuum pump, charging cylinder, and manifold gauge set.
- Connect an R-134a service center to the low- and high-pressure service gauge port valves.
- Evacuate the system until the low-pressure gauge reads at least 99.4 kPa (29.5 in-Hg) of vacuum and as close as 101.1 kPa (30 in-Hg) as possible. Continue to operate the vacuum pump for a minimum of 45 minutes.
- Turn off the evacuation pump. Observe the low-pressure gauge for five minutes to make sure that the system vacuum is held. If vacuum is not held for five minutes, leak-test the system, service the leaks, and evacuate the system again.