Test Description
WARNING: This page is about a different car, the 2007 Saturn Vue. However, it is still accessible from the selected car via links, so may be relevant.
The numbers below refer to the step numbers on the diagnostic table.
- 1: This step determines if the A/C system has at least the minimum refrigerant charge required to operate the system without damage.
- 2: This step measures the performance of the A/C system.
- 3: This step is to allow for vehicle variations as well as high ambient temperatures.
Air Conditioning (A/C) System Performance Test (LAT)
| Step | Action | Values | Yes | No |
|---|---|---|---|---|
|
IMPORTANT:
|
||||
| 1 |
|
More than 16°C (60°F) - 345 kPa (50 psi) More than 24°C (75°F) - 483 kPa (70 psi) More than 33°C (90°F) - 690 kPa (100 psi) |
Go to Step 2 | Go to Leak Testing |
| 2 |
IMPORTANT:
Record the relative humidity and the ambient air temperature at the time of the test.
IMPORTANT:
Press the RESET button, before using the print function of the J 43600
. See Special Tools .
|
- | Go to Step 8 | Go to Step 3 |
| 3 | If the pressures and temperatures recorded do not fall within the specified ranges:
Does all the data recorded fall within the specified ranges of the A/C Performance Table? |
- | Go to Step 8 | Go to Step 4 |
| 4 | Do the high and low side pressures fall within the specified ranges, but the panel outlet temperatures do not? | - | Go to Air Conditioning (A/C) Diagnostics - Pressure Zone A | Go to Step 5 |
| 5 | Is the low side pressure greater than the specified range, but the high side pressure within or less than the specified range? | - | Go to Air Conditioning (A/C) Diagnostics - Pressure Zone B | Go to Step 6 |
| 6 | Are the low and high side pressures both greater than the specified ranges? | - | Go to Air Conditioning (A/C) Diagnostics - Pressure Zone C | Go to Step 7 |
| 7 | Is the high side pressure greater than the specified range, but the low side pressure is within or less than the specified range? | - | Go to Air Conditioning (A/C) Diagnostics - Pressure Zone D | Go to Step 8 |
| 8 | Operate the system in order to verify the test results. Did you find the same results? |
- | System OK | Go to Symptoms - HVAC Systems - Manual |
A/C Performance Table
| Ambient Temperature | Relative Humidity | Low Side Service Port Pressure | High Side Service Port Pressure | Maximum Left Center Discharge Air Temperature |
|---|---|---|---|---|
| 13-18°C (55-65°F) | 0-100% | 151-206 kPa (22-30 psi) | 799-1150 kPa (116-167 psi) | 8°C (45°F) |
| 19-24°C (66-75°F) | Below 40% | 151-213 kPa (22-31 psi) | 1057-1446 kPa (152-210 psi) | 8°C (45°F) |
| Above 40% | 151-234 kPa (22-34 psi) | 1061-1522 kPa (154-221 psi) | 10°C (50°F) | |
| 25-29°C (76-85°F) | Below 35% | 158-234 kPa (23-34 psi) | 1322-1688 kPa (192-245 psi) | 9°C (48°F) |
| 35-50% | 172-241 kPa (25-35 psi) | 1357-1743 kPa (197-253 psi) | 10°C (50°F) | |
| Above 50% | 179-254 kPa (26-37 psi) | 1391-1832 kPa (202-266 psi) | 13°C (55°F) | |
| 30-35°C (86-95°F) | Below 30% | 186-261 kPa (27-38 psi) | 1550-1970 kPa (225-286 psi) | 13°C (55°F) |
| 30-50% | 172-275 kPa (25-40 psi) | 1136-1591 kPa (165-231 psi) | 14°C (57°F) | |
| Above 50% | 186-310 kPa (27-45 psi) | 1291-1688 kPa (177-245 psi) | 17°C (61°F) | |
| 36-41°C (96-105°F) | Below 20% | 192-289 kPa (28-42 psi) | 1371-1791 kPa (199-260 psi) | 14°C (57°F) |
| 20-40% | 206-316 kPa (30-46 psi) | 1398-1853 kPa (203-269 psi) | 17°C (61°F) | |
| Above 40% | 227-337 kPa (33-49 psi) | 1467-1901 kPa (213-276 psi) | 18°C (64°F) | |
| 42-46°C (106-115°F) | Below 20% | 234-323 kPa (34-47 psi) | 1681-2039 kPa (244-296 psi) | 18°C (63°F) |
| Above 20% | 248-378 kPa (36-51 psi) | 1708-2087 kPa (248-303 psi) | 19°C (66°F) | |
| 47-49°C (116-120°F) | Below 30% | 282-378 kPa (41-55 psi) | 1956-2321 kPa (284-337 psi) | 22°C (70°F) |