The numbers below refer to the step numbers on the diagnostic table.
- 2: This step clears the HVAC control module memory and checks for current air temperature actuator diagnostic trouble codes.
- 3: Ambient air temperature must be above 3°C (38°F) in order for this A/C Compressor test to be run.
- 7: The specified values are from the A/C System Performance Test
Too Hot in Vehicle
| Step | Action | Values | Yes | No |
|---|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: The temperature cannot be adjusted, or the cooling is insufficient during A/C operation. |
||||
| 1 | Did you perform the HVAC Diagnostic System Check? | - | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 |
|
- | Go to Diagnostic Trouble Code (DTC) List | Go to Step 3 |
| 3 |
IMPORTANT:
Ambient air temperature must be above 3°C (38°F).
|
- | Go to Step 4 | Go to HVAC Compressor Clutch Does Not Engage |
| 4 | Place the blower motor switch in each speed position. Does the blower motor operate correctly for each speed position? |
- | Go to Step 5 | Go to Blower Motor Inoperative |
| 5 | Does the blower motor provide sufficient air flow? | - | Go to Step 6 | Go to Blower Motor Malfunction |
| 6 |
|
- | Go to Step 7 | Go to Air Recirculation Malfunction |
| 7 | Perform the A/C system performance test. Refer to Air Conditioning (A/C) System Performance Test
in Heating, Ventilation and Air Conditioning. Does the system pass the A/C System Performance Test? |
- | Go to Step 8 | Go to Air Conditioning (A/C) System Performance Test in Heating, Ventilation and Air Conditioning |
| 8 |
|
- | Go to Step 10 | Go to Step 9 |
| 9 | Inspect for a blocked or malfunctioning inside air temperature sensor. Refer to Inside Air Temperature Sensor Replacement . Did you find and correct the condition? |
- | Go to Step 20 | Go to Step 13 |
| 10 |
|
4.3 V | Go to Step 11 | Go to Step 15 |
| 11 |
|
- | Go to Step 12 | Go to Step 15 |
| 12 | Does the customer need to change the set temperature frequently to maintain comfort? | - | Go to Symptoms - HVAC Systems - Automatic | System OK |
| 13 | Inspect for poor connections at the harness connector of the inside air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 20 | Go to Step 14 |
| 14 |
|
- | Go to Step 16 | Go to Step 17 |
| 15 | Inspect for poor connections at the harness connector of the sunload sensor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 20 | Go to Step 18 |
| 16 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 20 | Go to Step 19 |
| 17 | Replace the inside air temperature sensor. Refer to Inside Air Temperature Sensor Replacement . Did you complete the replacement? |
- | Go to Step 20 | - |
| 18 | Replace the sunload sensor. Refer to Sun Load Sensor Replacement . Did you complete the replacement? |
- | Go to Step 20 | - |
| 19 |
IMPORTANT:
Perform the recalibration procedure for the HVAC control module. Replace the HVAC control module. Refer to HVAC Control Module Replacement .Did you complete the replacement? |
- | Go to Step 20 | - |
| 20 | Operate the system in order to verify the repair. Did you correct the condition? |
- | System OK | Go to Step 3 |