Diagnostic Aids
WARNING: This page is about a different car, the 2004 Chevrolet Corvette. However, it is still accessible from the selected car via links, so may be relevant.
- The range fault code can only be detected following a check of the air temperature actuator travel range. The air temperature actuator travel range check can only be initiated by disrupting power to the HVAC control module or with the scan tool.
- The calibration limit is 147-220 counts (2.9-4.4 V). An actual range below this limit suggests an obstruction, something stuck in the door limiting travel. An actual range above this limit suggests an over travel condition, damaged or missing foam seals.
- If condition not present, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
DTC B0441 or B0446
| Step | Action | Values | Yes | No |
|---|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views |
||||
| 1 | Did you perform the HVAC Diagnostic System Check? | - | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 |
|
147-220 counts | Go to Diagnostic Aids | Go to Step 3 |
| 3 | Test the ignition 3 voltage circuit of the appropriate air temperature actuator for an open or high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 13 | Go to Step 4 |
| 4 | Test the air temperature door control circuit of the appropriate air temperature actuator for an open, high resistance, short to ground or short to voltage. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 13 | Go to Step 5 |
| 5 | Test the 5 volt reference circuit of the appropriate air temperature actuator for an open or high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 13 | Go to Step 6 |
| 6 |
IMPORTANT:
The appropriate air temperature actuator connector and the HVAC control module connector must be connected to correctly perform test.
|
- | Go to Step 7 | Go to Step 9 |
| 7 |
|
0 V decreasing 5 V increasing 2.5 V stationary | Go to Step 8 | Go to Step 10 |
| 8 | Inspect the appropriate air temperature door and the appropriate air temperature actuator for the following conditions:
Did you find and correct the condition? |
- | Go to Step 13 | Go to Diagnostic Aids |
| 9 | Inspect for poor connections at the harness connector of the appropriate air temperature actuator. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 13 | Go to Step 11 |
| 10 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 13 | Go to Step 12 |
| 11 |
IMPORTANT:
Perform the recalibration procedure for the appropriate air temperature actuator. Replace the appropriate air temperature actuator. Refer to Air Temperature Actuator Replacement - Left or Air Temperature Actuator Replacement - Right .Did you complete the replacement? |
- | Go to Step 13 | - |
| 12 |
IMPORTANT:
Perform the recalibration procedure for the HVAC control module. Replace the HVAC control module. Refer to HVAC Control Module Replacement .Did you complete the replacement? |
- | Go to Step 13 | - |
| 13 |
|
- | Go to Step 2 | System OK |