Possible deviation from specified value during the pressure test (5 Of 9)
| Possible deviation from specified value during the pressure test |
|---|
|
| Possible causes for the deviation from specified value and their solutions |
|
| Final Procedures |
| -- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .-- Repeat the test. Refer to MECHANICALLY DRIVEN A/C COMPRESSOR, CHECKING PRESSURE WITH A/C SYSTEM SWITCHED ON . |
If there is too much refrigerant oil in the circuit, the A/C compressor must be emptied and the desiccant bag (the dryer cartridge) or the reservoir/receiver/dryer must be replaced. After cleaning (flushing with refrigerant R1234yf) (refer to REFRIGERANT CIRCUIT, CLEANING ) fill the refrigerant circuit with the correct quantity of refrigerant oil. Refer to REFRIGERANT OIL CAPACITIES (vehicle-specific Service Information) and Refrigerant Circuit (vehicle-specific Service Information).
With this malfunction, evaporator may ice up although the quantity of refrigerant in circuit is OK.
A malfunction on the Evaporator Vent Temperature Sensor -G263- can also cause icing-up of refrigerant circuit. For this concern also pay attention to the measured value of the Evaporator Vent Temperature Sensor -G263-. Use the Vehicle Diagnostic Tester in the "Guided Fault Finding" function of the A/C system and refer to Component Location Overview - A/C System (vehicle-specific Service Information).