On-Vehicle Inspection

WARNING: This page is about a different car, the 2008 Toyota RAV4. However, it is still accessible from the selected car via links, so may be relevant.
  1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET 
    1. This method uses a manifold gauge set to locate problem areas. Read the manifold gauge pressure when these conditions are established. Test conditions:
      • Temperature at the air inlet is 30 to 35°C (86 to 95°F).
      • Engine is running at 1,500 rpm.
      • All doors are fully open.
      • Blower speed control switch is at HI.
      • A/C switch is ON.

      Gauge readings (Reference).

      Fig 1: Identifying Blower Zone Graph - Pressure
      G04950499Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
      1. Normally functioning refrigeration system
        Fig 2: Identifying Manifold Gauge Set Different Position
        G04950500Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002

        Gauge reading 

        PRESSURE SIDE REFRIGERANT VOLUME CHART

        Pressure side Refrigerant volume
        Low 0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2 )
        High 1.37 to 1.57 MPa (14 to 16 kgf/cm2 )
      2. The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.
        Fig 3: Checking Refrigerant Pressure (Moisture In Refrigerant System)
        G04950501Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        During operation, pressure on low pressure side cycles between normal and vacuum Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored.
        • Drier is overly saturated
        • Moisture in refrigeration system freezes at expansion valve orifice and blocks refrigerant circulation
        1. Replace cooler drier
        2. Remove moisture from cycle by repeatedly evacuating air
        3. Supply appropriate volume of new refrigerant
      3. The A/C system does not function effectively due to insufficient cooling.
        Fig 4: Checking Refrigerant Pressure (Insufficient Cooling)
        G04950502Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        • Pressure low on both low and high pressure sides
        • Cooling performance insufficient
        Gas leakage from refrigeration system
        • Insufficient refrigerant
        • Refrigerant leakage
        1. Check for gas leakage and repair if necessary
        2. Supply appropriate volume of new refrigerant
        3. If indicated pressure value close to 0 when connected to gauge, create vacuum after inspecting and repairing the location of leakage
      4. The A/C system does not function effectively due to poor circulation of the refrigerant.
        Fig 5: Checking Refrigerant Pressure (Poor Circulation Of Refrigerant)
        G04950503Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        • Pressure low on both low and high pressure sides
        • Frost exists on piping from condenser to A/C unit
        Refrigerant flow obstructed by dirt in condenser Condenser clogged Replace condenser
      5. The A/C system does not function intermittently because the refrigerant does not circulate.
        Fig 6: Checking Refrigerant Pressure (Refrigerant Not Circulate)
        G04950504Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        • Vacuum indicated on low pressure side, and extremely low pressure indicated on high pressure side
        • Frost or condensation seen on piping on both sides of condenser or expansion valve
        • Refrigerant flow obstructed by moisture or dirt in refrigeration system
        • Refrigerant flow obstructed by gas leakage from expansion valve
        Refrigerant does not circulate
        1. Check expansion valve refrigerant
        2. Clean expansion valve by blowing air
        3. Replace condenser
        4. Evacuate air and charge appropriate volume of new refrigerant
        5. For gas leakage from expansion valve, replace expansion valve
      6. The A/C system does not function effectively due to overcharged refrigerant or insufficient cooling of the condenser.
        Fig 7: Checking Refrigerant Pressure (Overcharged Refrigerant Or Insufficient Cooling Of Condenser)
        G04950505Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        Pressure extremely high on both low and high-pressure sides
        • Excessive refrigerant
        • Cooling performance of condenser insufficient
        • Condenser is dirty
        • Condenser fan motor is malfunctioning
        • Excessive refrigerant
        1. Clean condenser
        2. Check condenser fan motor operation
        3. If 1 and 2 normal, check the amount of refrigerant and supply appropriate volume of refrigerant
      7. The A/C system does not function due to air in the refrigeration system.
        CAUTION: The low-pressure piping may be very hot and cause serious burns.
        Fig 8: Identifying Manifold Gauge Set Different Position
        G04950506Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        • Pressure extremely high on both low and high-pressure sides
        • Low-pressure piping is too hot to touch
        Air in refrigeration system
        • Air in refrigeration system
        • Vacuum purging insufficient
        1. Check if compressor oil is dirty or insufficient
        2. Evacuate air and charge new refrigerant
      8. The A/C system does not function effectively due to an expansion valve malfunction.
        Fig 9: Checking Refrigerant Pressure (Expansion Valve Malfunction)
        G04950507Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        • Pressure extremely high on both low and high-pressure sides
        • Frost or condensation on piping on low-pressure side
        Problem with expansion valve
        • Excessive refrigerant in low pressure piping
        • Expansion valve too wide open
        Replace expansion valve
      9. The A/C system does not function due to a defective compressor.
        Fig 10: Checking Refrigerant Pressure (Defective Compressor)
        G04950508Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
        SYMPTOMS CHART

        Symptoms Probable Cause Diagnosis Corrective Actions
        • Pressure extremely high on both low and high-pressure sides
        • Pressure extremely low on high pressure side
        Internal leakage in compressor
        • Compression failure
        • Leakage from damaged valve or broken sliding parts
        Repair or replace compressor