Low Pressure Solenoid Valve

  1. Visually check the LOW solenoid valve for cracks or other damage, and replace as necessary.
  2. Check the operation of the LOW solenoid valve when battery voltage is applied between the connector terminals.
    G13234304Courtesy of SUBARU OF AMERICA, INC.
    Terminal No. Inspection conditions Specification
    2 (+) - 1 (-) Apply battery voltage and discharge compressed air in the direction of the arrow. Must not discharge.
  3. If the check results show that it does not operate normally, replace the LOW solenoid valve.