Trouble causes
- UART communication failure
- A/C control panel failure
- Blower motor failure
- Intake door actuator failure
- Compressor failure
| Step | Check | Yes | No |
|---|---|---|---|
1 CHECK A/C CONTROL PANEL.
|
Does "Blower Fan Level" indicate 0, "Variable Flow Change Solenoid Duty" indicate 0% and "Fresh/Recircle Air Door Actuator Position Target" indicate 100% respectively? | Go to step 2 . | Replace the A/C control panel. Refer to REMOVAL . |
| 2 CHECK BLOWER MOTOR. With the OFF switch pressed, check the blower motor operation. |
Is the blower motor stopped? | Go to step 3 . | Refer to AIR GOES OUT OF CONTROL . |
| 3 CHECK INTAKE DOOR ACTUATOR. With the OFF switch pressed, check the FRESH/RECIRC door operation. |
Does the FRESH/RECIRC door set to FRESH? | Go to step 4 . | Refer to UNABLE TO SWITCH SUCTION VENTS . |
| 4 CHECK COMPRESSOR. With the OFF switch pressed, check the compressor operation. |
Is the compressor stopped? | System is normal. | Refer to COLD AIR DOES NOT COME OUT EVEN WHEN THE A/C SWITCH IS PRESSED. THE GLASS CANNOT BE DEFOGGED (COMPRESSOR DOES NOT OPERATE (VARIABLE)) . |