Remove/install refrigerant pressure sensor - AR83.30-P-5430MCC
MODEL 451.3/4 with CODE (I01) Air conditioning Plus
| Remove/install | |||
| Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerants. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been emptied. | AS83.00-Z-0001-01A | |
| Procedure for a damaged or leaky air conditioning system | AH83.30-N-0004-01A | ||
| Protect air conditioning circuit and components from moisture when carrying out repair work | AH83.30-N-0005-01A | ||
| Notes on handling R134a refrigerant | AH83.30-N-0003-01A | ||
| 1 | Remove front CBS | AR88.00-P-1010MCC | |
| 2 | Drain air conditioning system | AR83.30-P-1760MCC | |
| 3 | Disconnect electrical connector (1) from refrigerant pressure sensor (B12) | ||
| 4 | Remove refrigerant pressure sensor (B12) from refrigerant line (2) | ||
| *BA83.30-P-1001-01L | |||
| 5 | Remove filter dryer | AR83.30-P-6525MCC | |
| 6 | Install in the reverse order |
AIR CONDITIONING
| Number | Designation | Model 451.3/4 except 451.390/490 | Model 451.390/490 | |
|---|---|---|---|---|
| BA83.30-P-1001-01L | Refrigerant pressure sensor to AC line | Nm | 10 | 10 |