Installing Evaporator (Chiller)
NOTE:
NOTIFICATION
Opened refrigerant system for repairs.
Opened refrigerant system for repairs.
- Risk of moisture getting into the refrigerant system.
- Risk of contaminating the refrigerant circuit.
- Risk of saturation and irreparable damage to desiccator.
- Irreparable damage to the desiccator can damage the compressor and evaporator.
→ After opening the refrigerant circuit, close off the refrigerant lines/connections immediately using the relevant stoppers. To avoid contaminating the refrigerant circuit, the stoppers for the different refrigerants must be stored and used separately.
→ The desiccator must be replaced if the air humidity is high and if the refrigerant circuit is left open for a long time.
- Position evaporator (chiller) -1- with retaining clips -3- .
- Fit refrigerant line -1- on evaporator (chiller) -2- and expansion valve -3- .
- Tighten screws -2-
.
> Tightening torque 8 Nm (6 ftlb.)
Evaporator (chiller)
- Fit coolant hoses -1- on evaporator (chiller) -2- .
- Install evaporator (chiller) holder -1- .
- Fit refrigerant lines -1- on expansion valve -2- and evaporator (chiller) -3- .
- Fit coolant hoses -1 and 2- on voltage converter -3- .
- Fit coolant hoses -1- on cooler box holder -2- .
- Secure electric wire harness -1- .
- Install bulkhead -1- .