Both High- and Low-pressure Sides are Too Low

WARNING: This page is about a different car, the 2008 Nissan Maxima. However, it is still accessible from the selected car via links, so may be relevant.
BOTH HIGH- AND LOW-PRESSURE SIDES ARE TOO LOW

Gauge indication Refrigerant cycle Probable cause Corrective action
Both high- and low-pressure sides are too low.
G04878053Courtesy of NISSAN MOTOR CO., U.S.A.
  • There is a big temperature difference between liquid tank outlet and inlet. Outlet temperature is extremely low.
  • Liquid tank inlet and expansion valve are frosted.
Liquid tank inside is slightly clogged.
  • Replace liquid tank.
  • Check oil for contamination.
  • Temperature of expansion valve inlet is extremely low as compared with areas near liquid tank.
  • Expansion valve inlet may be frosted.
  • Temperature difference occurs somewhere in high-pressure side.
High-pressure pipe located between liquid tank and expansion valve is clogged.
  • Check and repair malfunctioning parts.
  • Check oil for contamination.
Expansion valve and liquid tank are warm or only cool when touched. Low refrigerant charge
↓
Leaking fittings or components
Check refrigerant for leaks. Refer to "CHECKING FOR REFRIGERANT LEAKS ".
There is a big temperature difference between expansion valve inlet and outlet while the valve itself is frosted. Expansion valve closes a little compared with the specification.
↓
  1. Improper expansion valve adjustment
  2. Malfunctioning expansion valve
  3. Outlet and inlet may be clogged.
  • Remove foreign particles by using compressed air.
  • Check oil for contamination.
An area of the low-pressure pipe is colder than areas near the evaporator outlet. Low-pressure pipe is clogged or crushed.
  • Check and repair malfunctioning parts.
  • Check oil for contamination.
Air flow volume is not enough or is too low. Evaporator is frozen.