64 50... A/C performance test (R 134a)

WARNING: This page is about a different variant/trim than selected.

Before A/C performance test, some conditions must be met 

  1. Provision of a BMW diagnostic system. Safeguard electrical system integrity by checking the fault memory (no faults in the fault memory).
  2. Provide a thermometer with separate gauge.
  3. Perform the test in a suitable workshop area with an ambient temperature between 20 °C and 30 °C.

Re 1:

Connect BMW diagnostic system to vehicle and display evaporator temperature.

Re 2:

Position a thermometer with a separate gauge approx. 5 cm below the roof liner at the height of the B-pillar. Lay gauge outwards out of vehicle interior.

Re 3:

Heating up the passenger compartment:

Air-conditioning performance test 

Turn on A/C compressor at a vehicle interior temperature of 50 °C.

After 3 to 4 minutes, the evaporator sensor temperature must be ≤ 15 °C.

DRAW OFF AIR CONDITIONING  if this temperature is not reached. Measure amount of refrigerant drawn off.

If drawn-off quantity does not correspond to SPECIFIED FILL QUANTITY : supplement refrigerant and repeat test.

If fill quantity is correct, continue troubleshooting by pressure measurement.

NOTE: Air conditioning with uncontrolled compressors only:
If necessary, then continue troubleshooting by pressure measurement.