Pinpoint Test C: DTC B2266 Or B2267
- C1 CHECK THE FEEDBACK POTENTIOMETER TOTAL RESISTANCE
- Disconnect: HVAC Module C228a
- Disconnect: HVAC Module C228b
- Measure the resistance between HVAC module C228b-8, circuit 436 (RD/LG), harness side and HVAC module C228a-20, circuit 438 (RD/WH), harness side.
- Is the resistance greater than 500 ohms?
- YES
: If diagnosing DTC B2266
, Go to C2.
If diagnosing DTC B2267 , Go to C3.
- NO : CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuits 436 (RD/LG) and 438 (RD/WH) for a short together. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
- C2 CHECK POTENTIOMETER LOW- AND HIGH-SIDE RESISTANCE
- Measure the low-side resistance between HVAC module C228b-4, circuit 437 (YE/LG), harness side and HVAC module C228a-20, circuit 438 (RD/WH), harness side.
- Measure the high-side resistance between HVAC module C228b-4, circuit 437 (YE/LG), harness side and HVAC module C228b-8, circuit 436 (RD/LG), harness side.
- Is the resistance between 250 and 5,500 ohms?
- YES : Go to C4.
- NO
: If the low-side
resistance only is greater than 5,500 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuit 438 (RD/WH) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the low-side resistance only is less than 250 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuits 437 (YE/LG) and 438 (RD/WH) for a short together. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the high-side resistance only is greater than 5,500 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuit 436 (RD/LG) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the high-side resistance only is less than 250 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuits 437 (YE/LG) and 436 (RD/LG) for a short together. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the high-side and low-side resistance is greater than 5,500 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests If the actuator tests OK, REPAIR circuit 437 (YE/LG) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
- C3 CHECK POTENTIOMETER LOW- AND HIGH-SIDE RESISTANCE
- Measure the low-side resistance between HVAC module C228b-5, circuit 1122 (RD), harness side and HVAC module C228a-20, circuit 438 (RD/WH), harness side.
- Measure the high-side resistance between HVAC module C228b-5, circuit 1122 (RD), harness side and HVAC module C228b-8, circuit 436 (RD/LG), harness side.
- Is the resistance between 250 and 5,500 ohms?
- YES : Go to C4.
- NO
: If the low-side
resistance only is greater than 5,500 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuit 438 (RD/WH) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the low-side resistance only is less than 250 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuits 1122 (RD) and 438 (RD/WH) for a short together. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the high-side resistance only is greater than 5,500 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuit 436 (RD/LG) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the high-side resistance only is less than 250 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests . If the actuator tests OK, REPAIR circuits 1122 (RD) and 436 (RD/LG) for a short together. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
If the high-side and low-side resistance is greater than 5,500 ohms, CARRY OUT the Blend Door Actuator component test under Component Tests If the actuator tests OK, REPAIR circuit 1122 (RD) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
- C4 CHECK CIRCUITS 436 (RD/LG), 437 (YE/LG) AND 1122 (RD) FOR A SHORT TO GROUND
- Measure the resistance between ground and the following:
- HVAC module C228b-8, circuit 436 (RD/LG), harness side.
- For DTC B2266 , HVAC module C228b-4, circuit 437 (YE/LG), harness side.
- For DTC B2267 , HVAC module C228b-5, circuit 1122 (RD), harness side.
- Is the resistance greater than 10,000 ohms?
- YES : Go to C5.
- NO : REPAIR circuit(s) for a short to ground. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
- Measure the resistance between ground and the following:
- C5 CHECK CIRCUITS 438 (RD/WH), 437 (YE/LG) AND 1122 (RD) FOR A SHORT TO VOLTAGE
- Measure the voltage between ground and the following:
- HVAC module C228a-20, circuit 438 (RD/WH), harness side.
- For DTC B2266 , HVAC module C228b-4, circuit 437 (YE/LG), harness side.
- For DTC B2267 , HVAC module C228b-5, circuit 1122 (RD), harness side.
- Is any voltage present?
- Measure the voltage between ground and the following:
- C6 CHECK THE BLEND DOOR ACTUATOR OPERATION NOTE: If a jumper fuse opens while carrying out this test step, repair the circuit(s) for a short.
- Key in ON position.
- Connect a fused jumper wire between:
- HVAC module C228a-13, circuit 246 (VT), harness side and HVAC module C228b-11, circuit 1566 (RD/YE), harness side.
- HVAC module C228a-26, circuit 245 (BN/LG), harness side and HVAC module C228a-2, circuit 57 (BK), harness side.
- Remove the fused jumpers.
- Measure the resistance between HVAC module C228b-4, circuit 437 (YE/LG), harness side and HVAC module C228a-20, circuit 438 (RD/WH), harness side.
- Connect a fused jumper wire between:
- HVAC module C228a-11, circuit 1124 (WH), harness side and HVAC module C228b-11, circuit 1566 (RD/YE), harness side.
- HVAC module C228a-12, circuit 1125 (BN), harness side and HVAC module C228a-2, circuit 57 (BK), harness side.
- Remove the fused jumpers.
- Connect a fused jumper wire between:
- HVAC module C228a-13, circuit 246 (VT), harness side and HVAC module C228b-11, circuit 1566 (RD/YE), harness side.
- HVAC module C228a-26, circuit 245 (BN/LG), harness side and HVAC module C228a-2, circuit 57 (BK), harness side.
- Does the resistance increase and decrease when the jumpers are connected?
- C7 CHECK THE BLEND DOOR ACTUATOR OPERATION NOTE: If a jumper fuse opens while carrying out this test step, repair the circuit(s) for a short.
- Key in ON position.
- Connect a fused jumper wire between:
- HVAC module C228a-26, circuit 245 (BN/LG), harness side and HVAC module C228b-11, circuit 1566 (RD/YE), harness side.
- HVAC module C228a-13, circuit 246 (VT), harness side and HVAC module C228a-2, circuit 57 (BK), harness side.
- Remove the fused jumpers.
- Measure the resistance between HVAC module C228b-5, circuit 1122 (RD), harness side and HVAC module C228a-20, circuit 438 (RD/WH), harness side.
- Connect a fused jumper wire between:
- HVAC module C228a-12, circuit 1125 (BN), harness side and HVAC module C228b-11, circuit 1566 (RD/YE), harness side.
- HVAC module C228a-11, circuit 1124 (WH), harness side and HVAC module C228a-2, circuit 57 (BK), harness side.
- Remove the fused jumpers.
- Connect a fused jumper wire between:
- HVAC module C228a-26, circuit 245 (BN/LG), harness side and HVAC module C228b-11, circuit 1566 (RD/YE), harness side.
- HVAC module C228a-13, circuit 246 (VT), harness side and HVAC module C228a-2, circuit 57 (BK), harness side.
- Does the resistance increase and decrease when the jumpers are connected?
- C8 CHECK THE ACTUATOR MOTOR DRIVE CIRCUITS FOR AN OPEN NOTE: Due to limited connector accessibility, before carrying out this test step, visually inspect the wiring between the HVAC module and actuator for opens or shorts. If no damage is visually evident, proceed with the test.
- Key in OFF position.
- Disconnect: For DTC B2266, LH Temperature Blend Door Actuator C2091
- Disconnect: For DTC B2267, RH Temperature Passenger Blend Door Actuator C2092
- Measure the resistance between HVAC module C228a-26, circuit 245 (BN/LG), harness side and the LH temperature blend door actuator C2091-6, circuit 245 (BN/LG), harness side.
- Measure the resistance between HVAC module C228a-13, circuit 246 (VT), harness side and the LH temperature blend door actuator C2091-1, circuit 246 (VT), harness side.
- Measure the resistance between HVAC module C228a-12, circuit 1125 (BN), harness side and the RH temperature blend door actuator C2092-6, circuit 1125 (BN), harness side.
- Measure the resistance between HVAC module C228a-11, circuit 1124 (WH), harness side and the RH temperature blend door actuator C2092-1, circuit 1124 (WH), harness side.
- Is the resistance less than 5 ohms?
NOTE: For DTC B2266 only.NOTE: For DTC B2266 only.NOTE: For DTC B2267 only.NOTE: For DTC B2267 only.- YES : INSPECT for binding or broken linkage. REPAIR as necessary. If no condition is found, INSTALL a new door actuator. TEST the system for normal operation.
- NO : REPAIR the circuit(s) for an open. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.
- C9 CHECK HVAC MODULE CONNECTION
- Carry out the HVAC Module Cold Boot Process .
- Carry out the HVAC Module Self-Test .
- Operate the system.
- Does the concern return?
- YES : INSTALL a new HVAC module. REFER to CLIMATE CONTROL article. TEST the system for normal operation.
- NO : The system is operating correctly at this time. The concern may have been caused by a loose or corroded connector. CLEAR the DTCs. REPEAT the self-test. TEST the system for normal operation.