Remove and install drier cartridge - AR83.30-P-6521V
MODEL 171.4 (except 171.473) with CODE (580) Automatic air conditioning with CODE (581) Comfort automatic air conditioning
| Remove/install | |||
|---|---|---|---|
| Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged. | - | |
| Conduct if air conditioning system is damaged or leaking | All models | AH83.30-N-0004-01A | |
| Protect air conditioning circuit and components from moisture when carrying out repair work | All models fitted with air conditioning | AH83.30-N-0005-01A | |
| Notes on handling refrigerant R134a | Air conditioning system with refrigerant R134a | AH83.30-N-0003-01A | |
| 1 | Discharge air conditioning system | AR83.30-P-1760V | |
| 2 | Connect air conditioning suction off, preparation and filling equipment for refrigerant R134a on the service valve (2) | *WE58.40-Z-1002-22A | |
| 3 | Unscrew sealing plug (3) from condenser (4) | ||
| *BA83.30-P-1006-01D | |||
| Fig 2 | |||
| 4 | Pull drier cartridge (1) out of condenser (4). | ||
| 5 | Install in the reverse order |
AIR CONDITIONING SYSTEM
| Number | Designation | Model 171 except 171.473 | |
|---|---|---|---|
| BA83.30-P-1006-01D | Sealing plugs at capacitor | Nm | 20 |
WORKSHOP EQUIPMENT
| WE58.40-Z-1002-22A | Air conditioning service station |