Diagnostic Procedure
WARNING: This page is about a different car, the 2005 Mazda MX-5 Miata. However, it is still accessible from the selected car via links, so may be relevant.
AIR FROM VENTS NOT COLD ENOUGH - DIAGNOSTIC PROCEDURE
| STEP | INSPECTION | ACTION | |
|---|---|---|---|
| 1 | CHECK TO SEE WHETHER VENT AIR TEMPERATURE IS NORMAL OR NOT
|
Yes | Operation is normal. (To prevent evaporator within cooling unit from freezing, A/C compressor stops right away when vent air temperature is 6 °C {43 °F} or less. |
| No | Go to next step. | ||
| 2 | INSPECT REFRIGERANT SYSTEM PERFORMANCE
|
Yes | Operation is normal. (Reinspect malfunction symptoms.) |
| No | Go to next step. | ||
| 3 | INSPECT DRIVE BELT
|
Yes | Go to next step. |
| No | Adjust or replace drive belt, then go to Step 20. (See DRIVE BELT ADJUSTMENT .) |
||
| 4 | CHECK TO SEE MALFUNCTION IS IN BLOWER UNIT INTAKE AND CONDENSER OR ANOTHER
|
Yes | Go to next step. |
| No | Go to Step 7. | ||
| 5 | INSPECT BLOWER UNIT INTAKE
|
Yes | Remove obstruction, then go to Step 20.(If air does not reach evaporator within cooling unit, heat exchange does not occur and refrigerant pressure becomes high. Therefore, removal of obstruction is necessary.) |
| No | Go to next step. | ||
| 6 | INSPECT CONDENSER
|
Yes | Adjust refrigerant to specified amount, then go to Step 20.(Excessive amount of refrigerant.) |
| No | Replace condenser, or repair and clean condenser fins, then go to Step 20. | ||
| 7 | CHECK TO SEE IF MALFUNCTION IS IN EXPANSION VALVE, RECEIVER/DRIER AND REFRIGERANT LINES OR ELSEWHERE
|
Yes | Go to next step. |
| No | Go to Step 13. | ||
| 8 | CHECK TO SEE IF MALFUNCTION IS IN EXPANSION VALVE AND RECEIVER/DRIER OR ELSEWHERE
|
Yes | Go to next step. |
| No | Go to Step 11. | ||
| 9 | CHECK TO SEE IF MALFUNCTION IS IN EXPANSION VALVE OR RECEIVER/DRIER
|
Yes | Go to next step. |
| No | Replace receiver/drier, then go to Step 20.(Since water has intermixed in receiver/drier, replacement is necessary.) | ||
| 10 | VERIFY THAT EXPANSION VALVE HEAT-SENSING TUBE WITHIN COOLING UNIT IS POSITIONED SECURELY AND CORRECTLY
|
Yes | Replace expansion valve, then go to Step 20.(Since valve closes too much, replacement is necessary.) |
| No | Install heat-sensing tube securely in proper position, then go to Step 20. | ||
| 11 | INSPECT REFRIGERANT LINES
|
Yes | If the vane makes a noise, add 10 ml {10 cc, 0.338 fl oz} of compressor oil to the A/C compressor. Verify that the noise is no longer heard. Adjust refrigerant to specified amounts, then go to Step 20. |
| No | If piping is damaged or cracked, replace it, then go to Step 20.If there is no damage, go to next step. | ||
| 12 | INSPECT PIPING CONNECTIONS FOR LOOSENESS
|
Yes | Tighten connections to specified torque. If the vane makes a noise, add 10 ml {10 cc, 0.338 fl oz} of compressor oil to the A/C compressor. Verify that the noise is no longer heard. Adjust refrigerant to specified amounts, then go to Step 20. If the vane makes a noise, add 10 ml {10 cc, 0.338 fl oz} of compressor oil to A/C compressor. Verify that the noise is no longer heard. |
| No | Replace O-ring on piping, adjust refrigerant to specified amounts, then go to Step 20. | ||
| 13 | CHECK TO SEE IF MALFUNCTION IS IN EXPANSION VALVE, AIR MIX ACTUATOR AND COMPRESSOR OIL OR ELSEWHERE
|
Yes | Go to next step. (Pressure hardly increases.) |
| No | Go to Step 16. | ||
| 14 | CHECK TO SEE IF MALFUNCTION IS IN COMPRESSOR OIL AMOUNT AND A/C COMPRESSOR OR ELSEWHERE
|
Yes | Return to Step 4. |
| No | Go to next step. | ||
| 15 | CHECK TO SEE IF MALFUNCTION IS IN COMPRESSOR OIL AMOUNT OR A/C COMPRESSOR
|
Yes | Troubleshooting completed. (Explain to customer that cause was insufficient compressor oil.) |
| No | Replace A/C compressor, then go to Step 20.(Cause is defective A/C compressor.) | ||
| 16 | CHECK TO SEE IF MALFUNCTION IS IN EXPANSION VALVE OR ELSEWHERE
|
Yes | Go to Step 19. |
| No | Go to next step. | ||
| 17 | VERIFY THAT AIR MIX ACTUATOR IS INSTALLED SECURELY AND PROPERLY
|
Yes | Go to next step. |
| No | Repair or install links, cranks and rods securely in proper position, then go to Step 20. | ||
| 18 | ADJUST COMPRESSOR OIL
|
Yes | Go to Step 20. |
| No | Readjust until compressor oil is 90 ml {100 cc, 3.0 fl oz}. | ||
| 19 | VERIFY THAT EXPANSION VALVE HEAT-SENSING TUBE WITHIN COOLING UNIT IS POSITIONED SECURELY AND CORRECTLY
|
Yes | Replace expansion valve, then go to next step. (Since valve opens too much, replacement is necessary.) |
| No | Install heat-sensing tube securely in proper position, then go to next step. | ||
| 20 | VERIFY THAT MALFUNCTION SYMPTOM DOES NOT OCCUR AFTER REPAIR
|
Yes | Troubleshooting completed. Explain repairs to customer. |
| No | Recheck malfunction symptoms, then repeat from Step 1 if malfunction recurs. | ||