Fluorescent Dye Injection - Using an R-134a Refrigerant Management Center and Dye/Lubricant Injector (Non-Hybrid Only)
WARNING: This page is about a different variant/trim than selected.
NOTE:
Do not add liquid-based R-134a Leak Detection Dye to the refrigerant system on hybrid vehicles equipped with an electric Air Conditioning (A/C) compressor. Liquid-based dyes are mixed with PAG oil, and will contaminate and damage the hybrid refrigerant system. Dye can only be added to hybrid vehicles by installing a new received/drier desiccant cartridge which includes a fluorescent dye "wafer" which will dissolve after approximately 30 minutes of continued A/C operation.
NOTE:
Fluorescent refrigerant system dye is added to the refrigerant system at the factory to assist in refrigerant system leak diagnosis using a Rotunda-approved UV blacklight. It is not necessary to add additional dye to the refrigerant system before diagnosing leaks, even if a significant amount of refrigerant has been removed from the system. Replacement receiver/drier desiccant cartridges are shipped with a fluorescent dye "wafer" included in the desiccant bag which will dissolve after approximately 30 minutes of continued A/C operation. It is not necessary to add dye after flushing or filtering the refrigerant system because a new receiver/drier desiccant cartridge is installed as part of the flushing or filtering procedure. Additional refrigerant system dye should only be added if more than 50% of the refrigerant system lubricant capacity has been lost due to a fitting separation, hose rupture or other damage.
NOTE:
This method of fluorescent dye injection requires the addition of R-134a from a R-134a Refrigerant Management Machine or R-134a Manifold Gauge Set hooked to an external tank to charge the dye into the refrigerant system. If adding fluorescent dye to a refrigerant system that is already fully charged, the R-134a Loop/Add On Injector Kit-Set method should be used.
NOTE:
Before using the R-134a Loop/Add On Injector Kit-Set for the first time, refer to the equipment manufacturer's instructions on evacuation of any non-condensable gases from the hoses.
NOTE:
Only connect the dye/lubricant injector from the R-134a Loop/Add On Injector Kit-Set when fluorescent dye is to be injected. The dye/lubricant injector has a one-way check valve that will prevent refrigerant system recovery and evacuation.
NOTE:
Refrigerant system pressure should be between 413-551 kPa (60-80 psi) at 24°C (75°F) with the engine off.
- Connect a R-134a Refrigerant Center or a R-134a Manifold Gauge Set to the refrigerant system service port valves.
- Verify that the valves on the dye/lubricant injector are closed.
- Fill the fluorescent dye injector reservoir with 7 ml (0.25 oz) of fluorescent dye.
- Install the dye/lubricant injector between the low-pressure service gauge port valve and the R-134a Refrigerant Center or R-134a Manifold Gauge Set.
- Open all valves and inject the fluorescent dye into the refrigerant system.
- When fluorescent dye injection is complete, close all valves.
- Recover the refrigerant from the dye/lubricant injector.
- Remove the dye/lubricant injector from the low-pressure service gauge port valve and the R-134a Refrigerant Center or R-134a Manifold Gauge Set.
NOTE:
If no R-134a pressure is present in the refrigerant system, the system should be evacuated before carrying out the injection procedure. For additional information, refer to AIR CONDITIONING (A/C) SYSTEM RECOVERY, EVACUATION AND CHARGING .
NOTE:
The dye/lubricant injector is included as part of the 219-00069 R-134a Loop/Add On Injector Kit-Set.