DTC P06A0-14: Compressor Solenoid Circuit Short to Ground or Open [11/2021 - ]: Procedure
WARNING: This page does not describe the selected car, but rather 8 other vehicles, including the 2025 Lexus NX 350, 2025 Lexus NX 250, 2024 Lexus NX 350, 2024 Lexus NX 250, and 2023 Lexus NX 350. However, it is still accessible from the selected car via links, so may be relevant.
- READ VALUE USING GTS
- Read the Data List according to the display on the GTS.
Body Electrical > Air Conditioner > Data List
Tester Display Measurement Item Range Normal Condition Diagnostic Note Solenoid Valve Control Current Value Solenoid valve control current Min.: 0 mA
Max.: 1000 mAValue changes between 0 A and 0.997 A in accordance with solenoid valve operation - Body Electrical > Air Conditioner > Data List
Tester Display Solenoid Valve Control Current Value OK
The display is as specified in the normal condition column.
Result
Proceed to OK NG
Result:
OK
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY. Refer to REMOVAL [11/2021 - ]
Result:
NG
See step 2
- Read the Data List according to the display on the GTS.
- INSPECT AIR CONDITIONING AMPLIFIER ASSEMBLY
- Disconnect the B56 compressor assembly with pulley connector.
- Measure the resistance according to the value(s) in the table below.
*a Component without harness connected
(Compressor Assembly with Pulley)Standard Resistance
Tester Connection Condition Specified Condition 1 (SOL-) - 2 (SOL+) Compressor temperature 25°C (77°F) 10.1 to 11.1 Ω Result
Proceed to OK NG
Result:
NG
REPLACE COMPRESSOR ASSEMBLY WITH PULLEY
for T24A-FTS: Refer to REMOVAL [11/2021 - ]
for A25A-FKS: Refer to REMOVAL [11/2021 - ]
Result:
OK
See step 3
- CHECK HARNESS AND CONNECTOR (COMPRESSOR ASSEMBLY WITH PULLEY - AIR CONDITIONING AMPLIFIER ASSEMBLY)
- Disconnect the B56 compressor assembly with pulley connector.
- Disconnect the D52 air conditioning amplifier assembly connector.
- Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection Condition Specified Condition B56-2 (SOL+) - D52-18 (SOL+) Always Below 1 Ω B56-1 (SOL-) - Body ground Always Below 1 Ω B56-2 (SOL+) or D52-18 (SOL+) - Other terminals and body ground Always 10 kΩ or higher Result
Proceed to OK NG
Result:
OK
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY. Refer to REMOVAL [11/2021 - ]
Result:
NG
REPAIR OR REPLACE HARNESS OR CONNECTOR