Symptom Table
WARNING: This page is about a different car, the 2016 Infiniti QX60. However, it is still accessible from the selected car via links, so may be relevant.
| Gauge indication | Refrigerant cycle | Probable cause | Corrective action |
|---|---|---|---|
| Both high and low pressure sides are too high. | The pressure returns to normal soon after sprinkling water on condenser. | Overfilled refrigerant. | Recover refrigerant, evacuate system, and recharge with the specified amount of refrigerant. Refer to RECYCLE REFRIGERANT . |
| Air flow to condenser is insufficient. | Insufficient condenser cooling performance.
|
|
|
| When compressor is stopped, a high - pressure reading quickly drops by approximately 196 kPa (2 kg/cm2 , 28 psi). It then gradually decreases. | Air mixed with refrigerant. | Recover refrigerant, evacuate system, and recharge with the specified amount of refrigerant. Refer to RECYCLE REFRIGERANT . | |
|
Expansion valve opened too much (excessive flow of refrigerant). | Replace expansion valve. | |
| High - pressure side is excessively high and low - pressure side is too low. | High - pressure pipe and upper side of condenser become hot, however, liquid tank does not become so hot. | Clogged or crushed high - pressure pipe located between compressor and condenser. | Repair or replace the malfunctioning parts. |
| High - pressure side is too low and low - pressure side is too high. |
|
Malfunction in compressor system (insufficient compressor pressure operation).
|
Replace compressor. Refer to REMOVAL AND INSTALLATION . |
| Both high and low pressure sides are too low. |
|
Clogged expansion valve.
|
Eliminate foreign material from expansion valve or replace it. |
|
Malfunction inside liquid tank (clogged strainer). | Replace condenser (includes liquid tank). Refer to REMOVAL AND INSTALLATION . | |
| Evaporator becomes frosted. | Clogged or crushed low - pressure pipe. | Repair or replace malfunctioning parts. | |
| Malfunction in intake air temperature sensor. | Check intake sensor system. Refer to DIAGNOSIS PROCEDURE . | ||
| There is a small temperature difference between the high and low pressure pipes for refrigerant cycle. |
|
|
|
| Low - pressure side sometimes becomes negative. |
|
|
|
| Hunting in high - pressure side. | There is no temperature difference between high and low - pressure sides. | Malfunctioning variable valve in compressor. |
|