Test Reading

RECIRCULATING-TO-DISCHARGE AIR TEMPERATURE

Inside air (Recirculating air) at blower assembly inlet Discharge air temperature at center ventilator
Relative humidity % Air temperature °C (°F) °C (°F)
50 - 60 20 (68) 5.1 - 7.1 (41 - 45)
25 (77) 8.4 - 10.9 (47 - 52)
30 (86) 14.5 - 17.5 (58 - 64)
60 - 70 20 (68) 7.1 - 9.1 (45 - 48)
25 (77) 10.9 - 13.4 (52 - 56)
30 (86) 17.5 - 20.5 (64 - 69)
AMBIENT AIR TEMPERATURE-TO-OPERATING PRESSURE

Ambient air High-pressure (Discharge side) kPa (kg/cm2 , psi) Low-pressure (Suction side) kPa (kg/cm2 , psi)
Relative humidity % Air temperature °C (°F)
50 - 70 20 (68) 822 - 1, 010 (8.4 - 10.3, 119.2 - 146.5) 215 - 265 (2.2 - 2.7, 31.2 - 38.4)
25 (77) 941 - 1, 151 (9.6 - 11.7, 136.5 - 166.9) 198 - 240 (2.0 - 2.4, 28.7 - 34.8)
30 (86) 1, 100 - 1, 348 (11.2 - 13.7, 159.5 - 195.5) 230 - 280 (2.3 - 2.9, 33.4 - 40.6)
35 (95) 1, 222 - 1, 498 (12.5 - 15.3, 177.2 - 217.3) 297 - 362 (3.0 - 3.7, 43.1 - 52.5)
40 (104) 1, 445 - 1, 770 (14.7 - 18.0, 209.6 - 256.7) 302 - 370 (3.1 - 3.8, 43.8 - 53.7)