Symptom Table
WARNING: This page is about a different car, the 2013 Infiniti FX50. However, it is still accessible from the selected car via links, so may be relevant.
| Gauge indication | Refrigerant cycle | Probable cause | Corrective action |
|---|---|---|---|
| Both high- and low-pressure sides are too high. | The pressure returns to normal is reduced soon after water is splashed on condenser. | Excessive refrigerant charge in refrigeration cycle. | Reduce refrigerant until specified pressure is obtained. |
| Air suction by cooling fan is insufficient. | Insufficient condenser cooling performance. ↓
|
|
|
|
Poor heat exchange in condenser (After compressor operation stops, high-pressure decreases too slowly). ↓ Air in refrigeration cycle. |
Evacuate repeatedly and recharge system. | |
| Engine tends to overheat. | Engine cooling systems malfunction. | Check and repair each engine cooling system. | |
|
↓ Improper expansion valve adjustment. |
Replace expansion valve. | |
| High-pressure side is too high and low-pressure side is too low. | Upper side of condenser and high-pressure side are hot, however, liquid tank is not so hot. | High-pressure tube or parts located between compressor and condenser are clogged or crushed. |
|
| High-pressure side is too low and low-pressure side is too high. | High- and low-pressure sides become equal soon after compressor operation stops. | Compressor pressure operation is improper. ↓ Damaged inside compressor packings. |
Replace compressor. |
| No temperature difference between high- and low-pressure sides. | Compressor pressure operation is improper. ↓ Damaged inside compressor packings. |
Replace compressor. | |
| Both high- and low-pressure sides are too low. |
|
Liquid tank inside is slightly clogged. |
|
|
High-pressure pipe located between liquid tank and expansion valve is clogged. |
|
|
| Expansion valve and liquid tank are warm or slightly cool when touched. | Low refrigerant charge. ↓ Leaking fittings or components. |
Check refrigerant for leakages. Refer to "REFRIGERANT LEAKAGES ". | |
| There is a big temperature difference between expansion valve inlet and outlet while the valve itself is frosted. | Expansion valve closes a little compared with the specification. ↓
|
|
|
| An area of the low-pressure pipe is colder than areas near the evaporator outlet. | Low-pressure pipe is clogged or crushed. |
|
|
| Air flow volume is not enough or is too low. | Evaporator is frozen. |
|
|
| Low-pressure side sometimes becomes negative. |
|
Refrigerant does not discharge cyclically. ↓ Moisture is frozen at expansion valve outlet and inlet. ↓ Water is mixed with refrigerant. |
|
| Low-pressure side becomes negative. | Liquid tank or front/rear side of expansion valve's pipe is frosted or wet with dew. | High-pressure side is closed and refrigerant does not flow. ↓ Expansion valve or liquid tank is frosted. |
Leave the system at rest until no frost is present. Start it again to check whether or not the malfunction is caused by water or foreign particles.
|