Precautions For Handling Leak Detector

WARNING: This page is about a different car, the 2013 Infiniti FX50. However, it is still accessible from the selected car via links, so may be relevant.

Use an electrical leak detector (SST: J-41995) or equivalent when performing a refrigerant leakage check. Ensure that the instrument is calibrated and set properly per the operating instructions.

The leak detector is a delicate device. Read the operating instructions and perform any specified maintenance for using the leak detector properly.

Fig 1: Identifying Electrical Leak Detector
G04877948Courtesy of NISSAN NORTH AMERICA, INC.
  1. Position probe approximately 3 mm (0.12 in) away from point to be checked.
    Fig 2: Positioning Probe Approximately 3 mm (0.12 in) Away From Point To Be Checked
    G05893404Courtesy of NISSAN NORTH AMERICA, INC.
  2. Circle each fitting completely with probe when testing.
    Fig 3: Circling Each Fitting Completely With Probe When Testing
    G04878151Courtesy of NISSAN NORTH AMERICA, INC.
  3. Move probe along component approximately 25 to 50 mm (1 to 2 in)/sec.
    Fig 4: Moving Probe Along Component Approximately 25 To 50 mm (1 To 2 in)/sec
    G04878152Courtesy of NISSAN NORTH AMERICA, INC.