| 0 |
Normal |
|
| 11 |
Interior Temperature Sensor Disconnection (OPEN, INCAR F/B Voltage ≥ 4.9V) |
|
| 12 |
Interior Temperature Sensor Short Circuit (SHORT, INCAR F/B Voltage ≤ 0.1V) |
|
| 13 |
External Temperature Sensor Disconnection (OPEN, AMBIENT F/B Voltage ≥ 4.9V) |
|
| 14 |
External Temperature Sensor Short Circuit (SHORT, AMBIENT F/B Voltage ≤ 0.1V) |
|
| 17 |
Evaporator Temperature Sensor Disconnection (OPEN, EVAP F/B Voltage ≥ 4.9V) |
|
| 18 |
Evaporator Temperature Sensor Short Circuit (SHORT, EVAP F/B Voltage ≤ 0.1V) |
|
| 19 |
Driver Seat Temperature Control Actuator Feedback Disconnection/Short Circuit (OPEN/SHORT) SHORT Range [TEMP F/B Voltage ≤ 0.1V] OPEN Range [TEMP F/B Voltage ≥ 4.9V] |
|
| 20 |
Driver Seat Temperature Control Actuator Motor Constraint (Note that if both the target and constraint ranges fall within the MAXCOOL range [0.1V < TEMP FB voltage ≤ 0.5V] and MAX WARM range [4.5V ≤ TEMP FB voltage < 4.9V], the error code 20 is not displayed because there is no longer any constraint. This will prevent MAX WARM and MAX COOL displaying the code 20 due to error margins of the Actuator and FATC.) |
f the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 21 |
Driver Seat Mode Actuator Feedback Disconnection/Short Circuit SHORT Range [DR MODE F/B Voltage ≤ 0.1V] OPEN Range [DR MODE F/B Voltage ≥ 4.9V] |
|
| 22 |
Driver Seat Mode Actuator Motor Constraint (Note that if both the target and constraint ranges fall within the VENT range [0.1V < DR MODE FB voltage ≤ 0.5V] and DEF range [4.5V ≤ DRMODE FB voltage < 4.9V], the error code 22 is not displayed because there is no longer any constraint. This will prevent VENT and DEF displaying the code 22 due to error margins of the Actuator and FATC.) |
f the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 24 |
Auto-defogging senor short circuit (when communication error occurs on sensor side for more than 5 seconds) or (ADS GLASS TEMP ≤ 0.1) or (ADS GLASS TEMP ≥ 4.9). |
ADS specification ONLY |
| 25 |
Internal/External Air Actuator Position Sensor Disconnection/Short Circuit SHORT Range [INTAKE F/B Voltage ≤ 0.1V] OPEN Range [INTAKE F/B Voltage ≥ 4.9V] |
|
| 26 |
Internal/External Air Actuator Motor Constraint (Note that if both the target and constraint ranges fall within the FRE range [0.1V < INTAKE FB voltage ≤ 0.5V] REC range [4.5V ≤ INTAKEFB voltage < 4.9V], the error code 26 is not displayed because there is no longer any constraint. This will prevent FRE and REC displaying the code 26 due to error margins of the Actuator and FATC.) |
f the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 32 |
Passenger Seat Temperature Control Actuator Feedback Disconnection/Short Circuit (OPEN/SHORT) SHORT Range [TEMP F/B Voltage ≤ 0.1V] OPEN Range [TEMP F/B Voltage ≥ 4.9V] |
|
| 33 |
Passenger Seat Temperature Control Actuator Motor Constraint (Note that if both the target and constraint ranges fall within the MAXCOOL range [0.1V < TEMP FB voltage ≤ 0.5V] and MAX WARM range [4.5V ≤ TEMP FB voltage < 4.9V], the error code 20 is not displayed because there is no longer any constraint. This will prevent MAX WARM and MAX COOL displaying the code 33 due to error margins of the Actuator and FATC.) |
If the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 34 |
Console temp door motor Disconnection/Short Circuit (OPEN/SHORT) SHORT Range [TEMP F/B Voltage ≤ 0.1V] OPEN Range [TEMP F/B Voltage ≥ 4.9V] |
|
| 35 |
Door motor stalling of console temp (The stalling judgement does not display the error code "35" in the control range [1.13V < TEMP F/B Voltage ≤ 1.53V] and the control range [4.5V ≤ TEMP F/B Voltage < 4.9V]. This is to avoid the error code "35" occurrence due to the FATC error). |
|
| 36 |
Console ON/OFF door Disconnection/Short Circuit (OPEN/SHORT) SHORT Range [TEMP F/B Voltage ≤ 0.1V] OPEN Range [TEMP F/B Voltage ≥ 4.9V] |
|
| 37 |
Rear Temp Door Motor Constraint (Note that if both the target and constraint ranges fall within the MAXCOOL range [0.1V < TEMP FB voltage ≤ 0.5V] and MAX WARM range [4.5V ≤ TEMP FB voltage < 4.9V], the error code 37 is not displayed because there is no longer any constraint. This will prevent MAX WARM and MAX COOL displaying the code 37 due to error margins of the Actuator and FATC.) |
f the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 38 |
Console Mode door Disconnection/Short Circuit (OPEN/SHORT) SHORT Range [TEMP F/B Voltage ≤ 0.1V] OPEN Range [TEMP F/B Voltage ≥ 4.9V] |
|
| 39 |
Console Mode Door Constraint (Note that if both the target and constraint ranges fall within the VENT [0.1V < MODE FB voltage ≤ 0.5V] and FLOOR [4.5V ≤ MODE FB voltage < 4.9V], the error code 39 is not displayed because there is no longer any constraint. This will prevent VENT and FLOOR displaying the code 39 due to error margins of the Actuator and FATC.) |
If the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 43 |
Defog door Disconnection/Short Circuit (OPEN/SHORT) SHORT Range [TEMP F/B Voltage ≤ 0.1V] OPEN Range [TEMP F/B Voltage ≥ 4.9V] |
|
| 44 |
Door motor stalling of defog (The stalling judgement does not display the error code "44" in the vent range [1.95V < DEF FB voltage ≤ 2.35V] and the DEF range [4.5V ≤ DEF FB voltage < 4.9V]. This is to avoid the error code "44" occurrence due to the errors of VENT, door of the DEF and the FATC). |
If the actuator cannot reach the desired control position in 10 seconds, then it is deemed constrained |
| 45 |
APT CAN Signal Error |
|
| 47 |
RPM CAN SIGNAL Error |
|
| 48 |
Vehicle Speed CAN Signal Error |
|
| 49 |
Engine coolant temperature CAN Signal Error |
|
| 61 |
Open/short circuit range of passenger seat mode door motor [TEMP F/B Voltage ≤ 0.1V] Open circuit range [TEMP F/B Voltage ≥ 4.9V] |
|
| 62 |
Mode door motor stalling of passenger seat (The stalling judgement does not display the error code "62" in the control range [0.1V < TEMP F/B Voltage ≤ 0.5V] and the control range [4.5V ≤ TEMP F/B Voltage < 4.9V]. This is to avoid the error code "62" occurrence due to the FATC error. |
|
| 68 |
FRONT Photo sensor LH CAN signal - CAN Signal error |
|
| 69 |
FRONT Photo sensor RH CAN signal - CAN Signal error |
|
| 71 |
ECV defect (If the ECV OPEN or the input current is less than 100 mA, it is judged as Fail.) |
|
| 72 |
Communication error between the rear control |
|
| 73 |
Communication error between the front control |
|
| 74 |
PM SENSOR Fail |
|
| 81 |
Open/short circuit range of console temp A door motor [TEMP F/B Voltage ≤ 0.1V] Open circuit range [TEMP F/B Voltage ≥ 4.9V] |
|
| 82 |
Door motor stalling of console temp A (The stalling judgement does not display the error code "82" in the control range [1.13V < TEMP F/B Voltage ≤ 1.53V] and the control range [4.5V ≤ TEMP F/B Voltage < 4.9V]. This is to avoid the error code "35" occurrence due to the FATC error. |
|
| 83 |
PM SENSOR High temperature operating condition (More than 85°C (135°F)) |
PM SENSOR specification ONLY |