Circuit/System Testing
WARNING: This page is about a different car, the 2008 GMC Sierra, 2008 GMC Cab & Chassis Sierra, 2008 Chevrolet Silverado, and 2008 Chevrolet Cab & Chassis Silverado. However, it is still accessible from the selected car via links, so may be relevant.
- Ignition OFF, disconnect the harness connector at the appropriate actuator.
- Test for less than 1 ohm between the low reference circuit terminal 7 and ground.
- If greater than the specified range, test the low reference circuit for an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- Ignition ON, test for 4.8-5.2 volts between the 5-volt reference circuit terminal 10 and ground.
- If less than the specified range, test the 5-volt reference circuit for a short to ground or an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- If greater than the specified range, test the 5-volt reference circuit for a short to voltage. If the circuit tests normal, replace the HVAC control module.
- Verify the appropriate scan tool parameter is less than 4 counts.
- If greater than the specified range, test the signal circuit terminal 9 for a short to ground. If the circuit tests normal, replace the HVAC control module.
- Install a 3-amp fused jumper wire between the signal circuit terminal 9 and the low reference circuit terminal. Verify the appropriate scan tool parameter is greater than 250 counts.
- If less than the specified range, test the signal circuit for a short to voltage or an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- Ignition ON, verify that a test lamp illuminates between the ignition circuit terminal 5 and ground.
- If the test lamp does not illuminate, test the ignition circuit for a short to ground or an open/high resistance.
- Install a DMM between the actuator control circuit terminal 6 and ground. While monitoring the DMM, use the scan tool to command the appropriate actuator from one direction to the other. The voltage on the control circuit should move from 0 volts in one direction to 5 volts in the other direction and 2.5 volts in the at rest state.
- If the voltage does not change, test the control circuit for an open, short to voltage or short to ground. If circuit tests normal replace the HVAC control module.
- If all circuits test normal, replace the actuator.