Test Description
WARNING: This page is about a different car, the 2004 GMC Sierra, 2004 GMC Cab & Chassis Sierra, 2004 Chevrolet Silverado, and 2004 Chevrolet Cab & Chassis Silverado. However, it is still accessible from the selected car via links, so may be relevant.
The numbers below refer to the step numbers on the diagnostic table.
- 6: The ambient air temperature must be above 5°C (40°F) in order for this A/C compressor test to be run.
- 8: This step ensures that the lower air temperature sensors operate properly. The LH and RH Heater Duct Actual parameter count values should lower as the air temperature of the ducts get warmer. If there is a high resistance in either of the air temperature sensors circuits or the sensor itself then the count value of the effected sensor would remain high.
- 9: This step ensures that the upper air temperature sensors operate properly. The LH and RH AC Duct Actual parameter count values should lower as the air temperature of the ducts get warmer. If there is a high resistance in either of the air temperature sensors circuits or the sensor itself then the count value of the effected sensor would remain high.
- 11: This action ensures that the internal fan of the inside air temperature sensor assembly is providing air flow across the internal sensor.
- 14: Use the following table to determine that the recorded scan tool values are within range for the recorded probe temperatures of the J 43600 .
Too Hot in Vehicle
| Temperature °C | Temperature °F | Scan Tool Display |
|---|---|---|
| 0-4 | 32-40 | 206-175 counts |
| 5-9 | 41-49 | 194-161 counts |
| 10-14 | 50-58 | 180-145 counts |
| 15-19 | 59-67 | 166-133 counts |
| 20-24 | 68-76 | 150-119 counts |
| 25-29 | 77-85 | 136-106 counts |
| 30-34 | 86-94 | 121-93 counts |
| 35-39 | 95-103 | 107-81 counts |
| 40-44 | 104-112 | 94-69 counts |
| 45-49 | 113-121 | 83-59 counts |
| 50-54 | 122-130 | 72-51 counts |
| 55-59 | 131-139 | 63-44 counts |
| 60-64 | 140-148 | 55-37 counts |
Too Hot in Vehicle
| Step | Action | Yes | No |
|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: Temperature can not be adjusted, or cooling insufficient during A/C operation. |
|||
| 1 | Did you perform the HVAC Diagnostic System Check? | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 |
IMPORTANT:
If during this diagnostic procedure the HVAC control module is disconnected a recalibration of actuators must be performed to avoid misdiagnosis.
|
Go to Diagnostic Trouble Code (DTC) List | Go to Step 3 |
| 3 |
|
Go to Step 4 | Go to Blower Motor Inoperative |
| 4 | Does the blower motor operate in each speed? | Go to Step 5 | Go to Blower Motor Malfunction |
| 5 |
|
Go to Step 6 | Go to Air Recirculation Malfunction |
| 6 |
|
Go to Step 7 | Go to HVAC Compressor Clutch Does Not Engage |
| 7 | Perform the refrigerant system performance test. Refer to Air Conditioning (A/C) System Performance Test (without PHT)Air Conditioning (A/C) System Performance Test (with PHT)
. Did you find and correct the condition? |
Go to Step 31 | Go to Step 8 |
| 8 |
|
Go to Step 9 | Go to Step 21 |
| 9 |
|
Go to Step 10 | Go to Step 21 |
| 10 | Check the air temperature sensors for proper installation. Refer to the following procedures:
Did you find and correct the condition? |
Go to Step 31 | Go to Step 11 |
| 11 |
|
Go to Step 12 | Go to Step 17 |
| 12 |
|
Go to Step 13 | Go to Step 25 |
| 13 |
|
Go to Step 14 | Go to Step 20 |
| 14 |
|
Go to Diagnostic Aids | Go to Step 15 |
| 15 |
|
Go to Step 16 | Go to Step 24 |
| 16 | Test the signal circuit and the low reference circuit of the suspect air temperature sensor for a high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 26 |
| 17 |
|
Go to Step 19 | Go to Step 18 |
| 18 | Test the fan motor supply voltage circuit of the inside air temperature sensor assembly for an open, a high resistance, or a short to ground. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 26 |
| 19 | Test the ground circuit of the inside air temperature sensor for an open or high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 23 |
| 20 |
|
Go to Step 22 | Go to Step 23 |
| 21 | Test the signal circuit and the low reference circuit of the appropriate air temperature sensor for a high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 24 |
| 22 | Test the signal circuit and the low reference circuit of the inside air temperature sensor for a high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 26 |
| 23 | Inspect for poor connections at the harness connector of the inside air temperature sensor assembly. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 29 |
| 24 | Inspect for poor connections at the harness connector of the appropriate air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 27 |
| 25 | Inspect for poor connections at the harness connector of the sunload sensor assembly. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 28 |
| 26 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
Go to Step 31 | Go to Step 30 |
| 27 | Replace the appropriate air temperature sensor. Refer to one of the following procedures:
Did you complete the replacement? |
Go to Step 31 | - |
| 28 | Replace the sunload sensor. Refer to Sun Load Sensor Replacement . Did you complete the replacement? |
Go to Step 31 | - |
| 29 | Replace the inside air temperature sensor. Refer to Inside Air Temperature Sensor Assembly Replacement . Did you complete the replacement? |
Go to Step 31 | - |
| 30 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? |
Go to Step 31 | - |
| 31 | Operate the system in order to verify the repair. Did you correct the condition? |
System OK | Go to Step 2 |