Test Description
WARNING: This page is about a different car, the 2004 Pontiac Aztek and 2004 Buick Rendezvous. However, it is still accessible from the selected car via links, so may be relevant.
The numbers below refer to the step numbers on the diagnostic table.
- 3: Tests for the proper operation of the circuit in the high voltage range.
- 4: Tests for the proper operation of the circuit in the low voltage range. If the fuse in the jumper opens when you perform this test, the signal circuit is shorted to voltage.
DTC B3933
| Step | Action | Value(s) | Yes | No |
|---|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views |
||||
| 1 | Did you perform the HVAC Diagnostic System Check? | - | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 |
|
-50°C (-58°F)-143°C (290°F) | Go to Diagnostic Aids | Go to Step 3 |
| 3 |
|
-43°C (-45°F) | Go to Step 5 | Go to Step 4 |
| 4 |
|
144°C (291°F) | Go to Step 8 | Go to Step 6 |
| 5 | Test the signal circuit of the evaporator temperature sensor for a short to ground. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 12 | Go to Step 9 |
| 6 | Test the signal circuit of the evaporator temperature sensor for a short to voltage, a high resistance, or an open. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 12 | Go to Step 7 |
| 7 | Test the low reference circuit of the evaporator temperature sensor for a high resistance or an open. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 12 | Go to Step 9 |
| 8 | Inspect for poor connections at the harness connector of the evaporator temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 12 | Go to Step 10 |
| 9 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 12 | Go to Step 11 |
| 10 | Replace the evaporator temperature sensor. Refer to Evaporator Temperature Sensor Replacement
in Heating, Ventilation and Air Conditioning. Did you complete the replacement? |
- | Go to Step 12 | - |
| 11 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? |
- | Go to Step 12 | - |
| 12 |
|
- | Go to Step 2 | System OK |