Diagnostic Aids
WARNING: This page is about a different car, the 2004 Pontiac Aztek and 2004 Buick Rendezvous. However, it is still accessible from the selected car via links, so may be relevant.
- A damaged or broken mode door and or actuator can cause this DTC to set.
- If the Mode actuator travels beyond it's calibrated limits the DTC will set.
DTC B0233
| Step | Action | Value(s) | Yes | No |
|---|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views |
||||
| 1 | Did you review the HVAC operation and perform the necessary inspections? | - | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 |
|
- | Go to Step 3 | Go to Step 4 |
| 3 | Inspect the mode door and the mode actuator for the following:
Did you find and correct the condition? |
- | Go to Step 15 | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems |
| 4 | Test the ignition 3 voltage circuit of the mode actuator for an open or a high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 5 |
| 5 | Test the ground circuit of the mode actuator for an open. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 6 |
| 6 | Test the 5 volt reference circuit of the mode actuator for an open, a high resistance, short to ground, or a short to voltage. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 7 |
| 7 | Test the mode door position signal circuit of the mode actuator for an open, a high resistance, short to ground, or a short to voltage. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 8 |
| 8 | Test the mode door control circuit of the mode actuator for an open, a high resistance, short to ground, or a short to voltage. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 9 |
| 09 |
IMPORTANT:
The mode actuator connector and the HVAC controller connector must be connected to correctly perform the test.
|
- | Go to Step 10 | Go to Step 11 |
| 10 |
|
0 V toward DEF 5 V toward FLR 2.5 V stationary |
Go to Step 11 | Go to Step 12 |
| 11 | Inspect for poor connections at the harness connector of the mode actuator. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 13 |
| 12 | Inspect for poor connections at the harness connector of the HVAC control assembly. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 15 | Go to Step 14 |
| 13 | Replace the mode actuator. Refer to Mode Actuator Replacement . Did you complete the replacement? |
- | Go to Step 15 | - |
| 14 | Replace the HVAC control assembly. Refer to HVAC Module Assembly Replacement
. Did you complete the replacement? |
- | Go to Step 15 | - |
| 15 | Operate the system in order to verify the repair. Did you correct the condition? |
- | System OK | Go to Step 2 |