Home >> Ford >> 2018 >> Taurus Limited, FWD, Gas >> Repair and Diagnosis >> External Pages >> Different car >> Section 32 (Climate Control System - General Information (2 Of 2)) >> Diagnosis And Testing >> Climate Control System - Vehicles With: Electronic Automatic Temperature Control (EATC) >> Pinpoint Tests >> Pinpoint Test Ad : C1B14:11, C1B14:12

Pinpoint Test Ad : C1B14:11, C1B14:12

WARNING: This page is about a different car, the 2018 Ford EcoSport. However, it is still accessible from the selected car via links, so may be relevant.
  1. Automatic Climate Control System for schematic and connector information.

    Normal Operation and Fault Conditions 

    A 5-volt reference voltage and ground is supplied to the climate control sensors and actuators from the HVAC control module.

    DTC Fault Trigger Conditions 

    DTC Description Fault Trigger Condition
    HVAC C1B14:11 Sensor Supply Voltage A: Circuit Short To Ground This DTC sets when the module senses less than 5 volts on the sensor reference voltage circuit, indicating a short to ground.
    HVAC C1B14:12 Sensor Supply Voltage A: Circuit Short To Battery This DTC sets when the module senses greater than 5 volts on the sensor reference voltage circuit, indicating a short to voltage.

    Possible Sources 

    • Wiring, terminals or connectors
    • HVAC control module

  2. NOTE: Use the correct probe adapter(s) when making measurements. Failure to. Use the correct probe adapter(s) may damage the connector.
  3. AD1 CHECK THE HVAC (HEATING, VENTILATION AND AIR CONDITIONING) CONTROL MODULE SELF-TEST

    • Ignition ON.

    • Using a diagnostic scan tool, perform HVAC control module self-test.

    Is DTC C1B14:11 present? 

    Yes  GO to  AD2
    No  GO to  AD5
  4. AD2 CHECK THE REFERENCE VOLTAGE CIRCUIT FOR A SHORT TO GROUND

    • Ignition OFF.

    • Disconnect HVAC control module C294A.

    • Measure:
      Positive Lead Measurement / Action Negative Lead
      Refer to C294A-3
      GFD328095Courtesy of FORD MOTOR COMPANY
      Ground

    Is the resistance greater than 10, 000 ohms? 

    Yes  GO to  AD3
    No  REPAIR the circuit.
  5. AD3 CHECK THE REFERENCE VOLTAGE CIRCUIT AND THE SIGNAL RETURN CIRCUIT FOR A SHORT TOGETHER

    • Ignition OFF.

    • Measure:
      Positive Lead Measurement / Action Negative Lead
      Refer to C294A-3
      GFD328095Courtesy of FORD MOTOR COMPANY
      Refer to C294A-2

    Is the resistance greater than 200 ohms? 

    Yes  GO to  AD6
    No  GO to  AD4
  6. AD4 CHECK THE A/C (AIR CONDITIONING) COMPONENTS

    • Measure:
      Positive Lead Measurement / Action Negative Lead
      Refer to C294A-3
      GFD328095Courtesy of FORD MOTOR COMPANY
      Refer to C294A-2

    • While measuring the resistance, disconnect the following components one at a time, in order. Stop disconnecting components if the measured resistance rises above 200 ohms.

      • (If equipped with air inlet door actuator with 5 circuits), Air inlet door actuator C289
      • Air distribution door actuator C236
      • Temperature door actuator C2093

    Did the resistance rise above 200 ohms? 

    Yes  INSTALL a new actuator (the last one to be disconnected). Refer to REMOVAL AND INSTALLATION  for the procedure. When installing an actuator, CONNECT the actuator electrical connector before the HVAC control module. This allows the actuator to be calibrated when the HVAC control module is connected.
    No  REPAIR the circuit.
  7. AD5 CHECK THE REFERENCE VOLTAGE CIRCUIT FOR A SHORT TO VOLTAGE

    • Ignition OFF.

    • Disconnect HVAC control module C228A.

    • Measure:
      Positive Lead Measurement / Action Negative Lead
      Refer to C294A-3
      GFD328094Courtesy of FORD MOTOR COMPANY
      Ground

    Is any voltage present? 

    Yes  REPAIR the circuit.
    No  GO to  AD6
  8. AD6 CHECK FOR CORRECT HVAC (HEATING, VENTILATION AND AIR CONDITIONING) CONTROL MODULE OPERATION

    • Ignition OFF.

    • Disconnect and inspect all HVAC control module electrical connectors (if not previously disconnected).

    • Repair:

      • corrosion (install new connector or terminal - clean module pins)
      • damaged or bent pins - install new terminals or pins
      • pushed-out pins - install new pins as necessary

    • Connect all HVAC control module electrical connectors. Make sure they seat and latch correctly.

    • Operate the system and determine if the concern is still present.

    Is the concern still present? 

    Yes  CHECK OASIS for any applicable Technical Service Bulletins (TSBs). If a TSB exists for this concern, DISCONTINUE this test and FOLLOW the TSB instructions. If no Technical Service Bulletins (TSBs) address this concern, INSTALL a new HVAC control module. REFER to: Heating, Ventilation and Air Conditioning (HVAC) Control Module .
    No  The system is operating correctly at this time. The concern may have been caused by a loose or corroded connector. ADDRESS the root cause of any connector or pin issues.