Pinpoint Test
- CHECK THE HVAC MODULE DTCs
- Ignition ON.
- Review the recorded DTCs from the HVAC module self-test.
Is DTC C1B14:11 present?
- Yes: GO to 2 .
- No: GO to 5.
- CHECK THE REFERENCE VOLTAGE CIRCUIT FOR A SHORT TO GROUND
- Ignition OFF.
- Disconnect: HVAC Module C228A.
- Disconnect: HVAC Module C228B.
- Disconnect: Auxiliary Climate Control Assembly.
- Measure:
HVAC Module Ground C228A Ground Pin Circuit Measurement / Action Pin Circuit 24 LH111 (BN/WH) - Ground
Is the resistance greater than 10, 000 ohms?
- Yes: GO to 3 .
- No: REPAIR the circuit.
- CHECK THE REFERENCE VOLTAGE CIRCUIT AND THE SIGNAL RETURN CIRCUIT FOR A SHORT TOGETHER
- Connect: Auxiliary Climate Control Assembly.
- Measure:
HVAC Module HVAC Module C228A C228A Pin Circuit Measurement / Action Pin Circuit 24 LH111 (BN/WH) 23 RH111 (GY/BU)
Is the resistance greater than 200 ohms?
- Yes: GO to 6.
- No: GO to 4 .
- CHECK THE ACTUATORS
- Measure:
HVAC Module HVAC Module C228A C228A Pin Circuit Measurement / Action Pin Circuit 24 LH111 (BN/WH) 23 RH111 (GY/BU) - While measuring the resistance, disconnect the components one at a time, in order. Stop disconnecting components if the measured resistance rises above 200 ohms:
- Defrost/panel/floor door actuator
- LH temperature blend door actuator
- RH temperature blend door actuator
- Recirculation door actuator
- In-vehicle temperature/humidity sensor
- Auxiliary mode door actuator
- Auxiliary temperature blend door actuator
- Auxiliary climate control assembly
Did the resistance rise above 200 ohms?
- Yes: INSTALL a new component in question (the last one to be disconnected).
- No: REPAIR the circuits.
- Measure:
- CHECK THE REFERENCE VOLTAGE CIRCUIT FOR A SHORT TO VOLTAGE
- Ignition OFF.
- Disconnect: HVAC Module C228A.
- Ignition ON.
- Measure:
HVAC Module Ground C228A Ground Pin Circuit Measurement / Action Pin Circuit 24 LH111 (BN/WH) - Ground
Is any voltage present?
- Yes: REPAIR the circuit.
- No: GO to 6 .
- CHECK FOR CORRECT HVAC MODULE OPERATION
- Ignition OFF.
- Disconnect and inspect all HVAC module connectors.
- Repair:
- corrosion (install new connector or terminals - clean module pins)
- damaged or bent pins - install new terminals/pins
- pushed-out pins - install new pins as necessary
- Reconnect the HVAC module connectors. Make sure they seat and latch correctly.
- Operate the system and determine if the concern is still present.
Is the concern still present?
- Yes: CHECK OASIS for any applicable TSBs . If a TSB exists for this concern, DISCONTINUE this test and FOLLOW TSB instructions. If no TSBs address this concern, INSTALL a new HVAC module. REFER to Heating Ventilation Air Conditioning (HVAC) Module .
- No: The system is operating correctly at this time. The concern may have been caused by module connections. ADDRESS the root cause of any connector or pin issues.