Normal Operation and Fault Conditions
When the A/C is requested, the FCIM sends the button press message over the I-CAN to the IPC. The IPC then sends the button press message to BCM over the HS-CAN . The BCM then sends the button press message to the HVAC module over the MS-CAN . Lastly the HVAC module sends an A/C request message through the MS-CAN to the BCM and the BCM sends the A/C request through the HS-CAN to the PCM.
REFER to Control System Logic
REFER to Controls and Compressor Cycling
When an A/C request is received by the PCM, the A/C compressor clutch only engages through the A/C clutch relay if all of the conditions are met:
- The PCM does not detect excessively high or low refrigerant pressure from the A/C pressure transducer.
- The PCM does not detect excessively high engine coolant temperature.
- The PCM does not detect an ambient air temperature below -1 C (30.2 F).
- The PCM has not detected a WOT condition.
- The HVAC module does not detect an evaporator discharge air temperature below 7.5 C (45.5 F).