Pinpoint Test

NOTE: The RH temperature blend door actuator connector in the pinpoint test is difficult to access. Before disconnecting the RH temperature blend door actuator, visually inspect the actuator and its harness for obvious damage. If no damage is evident, proceed with the test.
  1. CHECK THE HVAC MODULE FOR DTCs 
    1. Ignition ON.
    2. Using a scan tool, perform a HVAC module self-test.

    Are any DTCs present? 

    • Yes: For DTC B1082:11, GO to  3.

      For DTC B1082:12, GO to  4.

      For DTC B1082:13, GO to  5.

      For DTC B11E6:11, GO to  7.

      For DTC B11E6:15, GO to  9.

    • No: GO to .
  2. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR OPERATION USING ACTIVE COMMANDS
    1. Start the engine.
    2. Run the engine until it reaches normal operating temperature.
    3. Using a scan tool, view HVAC module PIDs  .
    4. Select PANEL mode on the HVAC controls.
    5. Select the highest blower motor setting.
    6. Monitor airflow while using the scan tool to operate the HVAC module active command RIGHT_BLEND, increasing and decreasing the percentage value.

    Does the airflow temperature change between warm and cold when the active command is changed? 

  3. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR MOTOR CIRCUITS FOR A SHORT TO GROUND
    1. Ignition OFF.
    2. Disconnect: HVAC Module C228B.
    3. Disconnect: RH Temperature Blend Door Actuator.
    4. Measure:
      HVAC Module Ground
      G08033185
      G08033186
      C228B Ground
      Pin Circuit Measurement / Action Pin Circuit
      13 CH213 (BN/GN)
      G08033187
      - Ground
      12 CH212 (BU/OG)
      G08033188
      - Ground

    Are the resistances greater than 10, 000 ohms? 

    • Yes: GO to  6.
    • No: REPAIR the circuit in question.
  4. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR MOTOR CIRCUITS FOR A SHORT TO VOLTAGE
    1. Ignition OFF.
    2. Disconnect: RH Temperature Blend Door Actuator.
    3. Disconnect: HVAC Module C228A.
    4. Disconnect: HVAC Module C228B.
    5. Ignition ON.
    6. Measure:
      HVAC Module Ground
      G08033189
      G08033190
      C228B Ground
      Pin Circuit Measurement / Action Pin Circuit
      13 CH213 (BN/GN)
      G08033191
      - Ground
      12 CH212 (BU/OG)
      G08033192
      - Ground

    Is any voltage present? 

    • Yes: REPAIR the circuit in question.
    • No: GO to  6.
  5. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR MOTOR CIRCUITS FOR AN OPEN
    1. Ignition OFF.
    2. Disconnect: HVAC Module C228B.
    3. Disconnect: RH Temperature Blend Door Actuator.
    4. Measure:
      HVAC Module RH Temperature Blend Door Actuator
      G08033193
      G08033194
      C228B C2092
      Pin Circuit Measurement / Action Pin Circuit
      12 CH212 (BU/OG)
      G08033195
      6 CH212 (BU/OG)
      13 CH213 (BN/GN)
      G08033196
      5 CH213 (BN/GN)

    Are the resistances less than 3 ohms? 

    • Yes: GO to  14.
    • No: REPAIR the circuit in question.
  6. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR MOTOR CIRCUITS FOR A SHORT TOGETHER
    NOTE: Access to the connector in the following step is difficult. Before carrying out this step, visually inspect the actuator and its harness for obvious damage. If no damage is evident, proceed with the test.
    1. Ignition OFF.
    2. Disconnect: RH Temperature Blend Door Actuator.
    3. Measure:
      HVAC Module HVAC Module
      G08033197
      G08033198
      C228B C228B
      Pin Circuit Measurement / Action Pin Circuit
      12 CH212 (BU/OG)
      G08033199
      13 CH213 (BN/GN)

    Is the resistance greater than 10, 000 ohms? 

    • Yes: GO to  14.
    • No: REPAIR the circuits.
  7. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR FEEDBACK CIRCUIT FOR A SHORT TO GROUND
    1. Ignition OFF.
    2. Disconnect: RH Temperature Blend Door Actuator.
    3. Disconnect: HVAC Module C228A.
    4. Disconnect: HVAC Module C228B.
    5. Measure:
      HVAC Module Ground
      G08033200
      G08033201
      C228B Ground
      Pin Circuit Measurement / Action Pin Circuit
      4 VH441 (WH/BN)
      G08033202
      - Ground

    Is the resistance greater than 10, 000 ohms? 

    • Yes: GO to .
    • No: REPAIR the circuit.
  8. CHECK THE SIGNAL RETURN CIRCUIT FOR A SHORT TO THE RH TEMPERATURE BLEND DOOR ACTUATOR FEEDBACK CIRCUIT
    1. Measure:
      HVAC Module HVAC Module
      G08033203
      G08033204
      C228A C228B
      Pin Circuit Measurement / Action Pin Circuit
      23 RH111 (GY/BU)
      G08033205
      4 VH441 (WH/BN)

    Is the resistance greater than 10, 000 ohms? 

    • Yes: GO to  14.
    • No: REPAIR the circuits.
  9. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR FEEDBACK CIRCUIT FOR A SHORT TO VOLTAGE
    1. Ignition OFF.
    2. Disconnect: HVAC Module C228A.
    3. Disconnect: HVAC Module C228B.
    4. Disconnect: RH Temperature Blend Door Actuator.
    5. Ignition ON.
    6. Measure:
      HVAC Module Ground
      G08033206
      G08033207
      C228B Ground
      Pin Circuit Measurement / Action Pin Circuit
      4 VH441 (WH/BN)
      G08033208
      - Ground

    Is any voltage present? 

    • Yes: REPAIR the circuit.
    • No: GO to 10  .
  10. CHECK THE REFERENCE VOLTAGE CIRCUIT FOR AN OPEN
    1. Ignition OFF.
    2. Measure:
      HVAC Module RH Temperature Blend Door Actuator
      G08033209
      G08033210
      C228A C2092
      Pin Circuit Measurement / Action Pin Circuit
      24 LH111 (BN/WH)
      G08033211
      1 LH111 (BN/WH)

    Is the resistance less than 3 ohms? 

    • Yes: GO to 11  .
    • No: REPAIR the circuit.
  11. CHECK THE REFERENCE VOLTAGE CIRCUIT FOR A SHORT TO THE RH TEMPERATURE BLEND DOOR ACTUATOR FEEDBACK CIRCUIT
    1. Ignition OFF.
    2. Measure:
      HVAC Module HVAC Module
      G08033212
      G08033213
      C228A C228B
      Pin Circuit Measurement / Action Pin Circuit
      24 LH111 (BN/WH)
      G08033214
      4 VH441 (WH/BN)

    Is the resistance greater than 10, 000 ohms? 

    • Yes: GO to 12  .
    • No: REPAIR the circuits.
  12. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR FEEDBACK CIRCUIT FOR AN OPEN
    1. Measure:
      HVAC Module RH Temperature Blend Door Actuator
      G08033215
      G08033216
      C228B C2092
      Pin Circuit Measurement / Action Pin Circuit
      4 VH441 (WH/BN)
      G08033217
      2 VH441 (VT/GN)

    Is the resistance less than 3 ohms? 

    • Yes: GO to 13  .
    • No: REPAIR the circuit.
  13. CHECK THE RH TEMPERATURE BLEND DOOR ACTUATOR RETURN SIGNAL RETURN CIRCUIT FOR AN OPEN
    1. Measure:
      HVAC Module RH Temperature Blend Door Actuator
      G08033218
      G08033219
      C228A C2092
      Pin Circuit Measurement / Action Pin Circuit
      23 RH111 (GY/BU)
      G08033220
      3 RH111 (GY/BU)

    Is the resistance less than 3 ohms? 

    • Yes: GO to 14  .
    • No: REPAIR the circuit.
  14. CHECK FOR CORRECT RH TEMPERATURE BLEND DOOR ACTUATOR OPERATION
    1. Disconnect and inspect the RH temperature blend door actuator connector.
    2. Repair:
      • corrosion (install new connector or terminals - clean module pins)
      • damaged or bent pins - install new terminals/pins
      • pushed-out pins - install new pins as necessary
    3. Reconnect the RH temperature blend door actuator connector. Make sure it seats and latches correctly.
    4. Reconnect the HVAC module connectors. Make sure they seat and latch correctly.
    5. Operate the system and determine if the concern is still present.

    Is the concern still present? 

    • Yes: INSTALL a new RH Temperature Blend Door Actuator, REFER to Temperature Blend Door Actuator - RH . TEST the system for normal operation. If the concern is still present, GO to 15  .
    • No: The system is operating correctly at this time. The concern may have been caused by module connections. ADDRESS the root cause of any connector or pin issues.
  15. MODULE ACTUATOR POSITION CALIBRATION
    NOTE: The purpose of the module actuator position calibration is to allow the HVAC module to reinitialize and calibrate the actuator stop points.
    1. Ignition OFF.
    2. Disconnect and inspect all HVAC module connectors.
    3. Repair:
      • corrosion (install new connector or terminals - clean module pins)
      • damaged or bent pins - install new terminals/pins
      • pushed-out pins - install new pins as necessary
    4. Reconnect the HVAC module connectors. Make sure they seat and latch correctly.
    5. Clear the DTCs  .
    6. Using a scan tool, perform HVAC Module self-test.
    7. Select any position except OFF
    8. NOTE: The HVAC module initializes and calibrates the actuators. Calibration of the actuators will take approximately 30 seconds.

      Operate the system and verify the concern is still present.

    Is the concern still present? 

    • Yes: CHECK OASIS  for any applicable TSBs  . If a TSB exists for this concern, DISCONTINUE this test and FOLLOW TSB instructions. If no TSBs  address this concern, INSTALL a new HVAC module. REFER to Heating Ventilation Air Conditioning (HVAC) Module .
    • No: The system is now operating correctly at this time. The concern may have been caused by a foreign object in the HVAC case or temporary binding that restricted actuator door travel. CHECK any actuator external linkage. If condition recurs, INSPECT actuator linkage and door for binding and CHECK HVAC case for foreign objects.