Home >> Ford >> 2009 >> Flex Limited, FWD >> Repair and Diagnosis >> External Pages >> Different car >> Section 1334 (HVAC Control System - General Information And Diagnostics) >> General Procedures >> Air Conditioning (A/C) System Recovery, Evacuation and Charging >> Refrigerant System Evacuation Using an R-134a Manifold Gauge Set

Refrigerant System Evacuation Using an R-134a Manifold Gauge Set

WARNING: This page is about a different car, the 2008 Mercury Sable, 2008 Ford Taurus X, and 2008 Ford Taurus. However, it is still accessible from the selected car via links, so may be relevant.
NOTE: Ford Motor Company recommends use of an R-134a Refrigerant Management Machine to carry out evacuation of the refrigerant system. If an R-134a Refrigerant Management Machine is not available, refrigerant system evacuation may be accomplished using a separate Vacuum Pump and R-134a Manifold Gauge Set.
NOTE: Leaks in refrigerant system service equipment, hoses or gauges can cause a leak in vacuum that may be misinterpreted as a problem with the vehicle's refrigerant system. It is necessary to leak-test all refrigerant system service equipment, hoses and gauges on a weekly basis to verify that no leaks are present.
  1. Connect the R-134a Manifold Gauge Set to the low-side and high-side service gauge port valves.
  2. Connect the center (yellow) hose from the R-134a Manifold Gauge Set to the suction port on the Vacuum Pump.
  3. Open all valves on the R-134a Manifold Gauge Set and both service gauge port valves.
  4. Turn on the Vacuum Pump and evacuate the system until the low-pressure gauge reads at least 99.4 kPa (29.5 in-Hg) of vacuum and as close to 101.1 kPa (30 in-Hg) as possible. Continue to operate the Vacuum Pump for a minimum of 45 minutes.
  5. Close the high-side and low-side valves on the R-134a Manifold Gauge Set (not the service gauge port valves) and turn OFF the Vacuum Pump.
  6. Observe the low-pressure gauge for 5 minutes to make sure that the system vacuum is held. If vacuum is not held for 5 minutes, leak test the system, repair the leak and evacuate the system again.