Home >> Ford >> 2006 >> Focus ZX5 SE, Standard >> Repair and Diagnosis >> External Pages >> Different car >> Section 489 (HVAC Control System-General Information And Diagnostics - F250-F550 Super Duty) >> General Procedures >> Air Conditioning (A/C) System Recovery, Evacuation and Charging >> Refrigerant System Recovery >> Notes

Refrigerant System Recovery: Notes

WARNING: This page is about a different car, the 2006 Ford Pickup, 2006 Ford F550 Super Duty, 2006 Ford F450 Super Duty, and 2006 Ford Cab & Chassis. However, it is still accessible from the selected car via links, so may be relevant.
NOTE: Ford Motor Company recommends use of an A/C service center to carry out recovery, evacuation and charging of the refrigerant system. If an A/C service center is not available, refrigerant system recovery, evacuation and charging may be accomplished using a separate recovery station, vacuum pump, charging meter and manifold gauge set.
NOTE: Leaks in refrigerant system service equipment, hoses or gauges can cause a leak in vacuum that may be misinterpreted as a problem with the vehicle's refrigerant system. It is necessary to leak-test all refrigerant system service equipment, hoses and gauges on a weekly basis to verify that no leaks are present.
  1. Prior to recovering, you must verify the purity of the refrigerant. For additional information, refer to REFRIGERANT IDENTIFICATION TESTING .
  2. Connect an R-134a refrigerant service center to the low- and high-pressure service gauge port valves following the operating instructions provided by the equipment manufacturer.
  3. Recover the refrigerant from the system following the operating instructions provided by the equipment manufacturer.
  4. Once the refrigerant service center has recovered the refrigerant, switch OFF the power supply.
  5. Allow the system to set for about 2 minutes, and observe the system vacuum reading. If the vacuum is not lost, disconnect the recovery equipment.
  6. If the system does lose vacuum, repeat Steps  3 through  5 until the vacuum level remains stable for 2 minutes.
  7. Carry out the required repairs.