Ford Motor Co.
- Connect hoses from Recovery/Recycling/Charging Center (023-00150) to high-side and low-side service valves. See SERVICE VALVE LOCATIONS under SYSTEM SERVICE VALVES.
- Turn equipment on and recover refrigerant according to equipment manufacturer's operating instructions. Allow equipment to operate until refrigerant is recovered. Close inlet valve (if equipped) on refrigerant recovery/recycling/charging center and turn equipment off.NOTE: On some applications, refrigerant recovery/recycling/charging center will automatically shut off through use of a low pressure switch. On other applications, refrigerant recovery/recycling/charging center must be manually shut off.
- Allow A/C system to remain closed for about 2 minutes while observing vacuum pressure readings. If vacuum pressure reading increases, repeat step 2 until vacuum pressure readings remain stable for 2 minutes. If vacuum pressure readings remain stable for 2 minutes, disconnect hoses from service ports and perform required A/C system repairs.