Home >> Ford >> 2000 >> Contour SE, 2.5 L, Standard >> Repair and Diagnosis >> External Pages >> Different car >> Section 1521 (HVAC Control System - General Information And Diagnostics - (Except Hybrid)) >> General Procedures >> Air Conditioning (A/C) System Recovery, Evacuation and Charging >> Refrigerant System Evacuation Using an R-134a Refrigerant Center

Refrigerant System Evacuation Using an R-134a Refrigerant Center

WARNING: This page is about a different car, the 2006 Mercury Mariner and 2006 Ford Escape. However, it is still accessible from the selected car via links, so may be relevant.
NOTE:
  • Use of a refrigerant center is recommended to carry out recovery, evacuation and charging of the refrigerant system. If a refrigerant center is not available, refrigerant system recovery, evacuation and charging may be accomplished using a separate recovery station, vacuum pump, charging meter and manifold gauge set.
  • Leaks in refrigerant system equipment, hoses or gauges can cause a leak in vacuum that may be misinterpreted as a problem with the vehicle refrigerant system. It is necessary to leak-test all refrigerant system equipment, hoses and gauges on a weekly basis to verify that no leaks are present.
  1. Connect an R-134a refrigerant center to the low pressure and high pressure gauge port valves following the operating instructions provided by the equipment manufacturer.
  2. Evacuate the system until the low-pressure gauge reads at least 99.4 kPa (29.5 in-Hg) of vacuum and as close to 101.1 kPa (30 in-Hg) as possible. Continue to operate the vacuum pump for a minimum of 45 minutes.
  3. Turn off the vacuum pump. Observe the low-pressure gauge for 5 minutes to make sure that the system vacuum is held. If vacuum is not held for 5 minutes, leak test the system, repair the leak and evacuate the system again.