Refrigerant Oil Capacity: Notes
When an A/C system is assembled at the factory, all components except the A/C compressor are refrigerant oil free. After the refrigerant system has been charged and operated, the refrigerant oil in the A/C compressor is dispersed throughout the refrigerant system. The receiver/drier, A/C evaporator, A/C condenser and the A/C compressor will each retain a significant amount of the needed refrigerant oil.
It is important to have the correct amount of refrigerant oil in the A/C system. This ensures proper lubrication of the A/C compressor. Too little oil will result in damage to the A/C compressor, while too much oil will reduce the cooling capacity of the A/C system and consequently result in higher discharge air temperatures.
It will not be necessary to check the oil level in the A/C compressor or to add oil, unless there has been an oil loss. An oil loss may occur due to a rupture or leak from a refrigerant line, a connector fitting, a component, or a component seal. If a leak occurs, add 30 milliliters (1 fluid ounce) of refrigerant oil to the refrigerant system after the repair has been made. Refrigerant oil loss will be evident at the leak point by the presence of a wet, shiny surface around the leak.
Refrigerant oil must be added when an A/C condenser, A/C evaporator or A/C receiver/drier is replaced (refer to the Refrigerant Oil Capacities chart).
The refrigerant oil level in a new A/C compressor must first be adjusted prior to compressor installation (refer to COMPRESSOR OIL DRAIN PROCEDURE ).
| COMPONENT | ml. | oz. |
|---|---|---|
| Total System Fill | 180 | 6.1 |
| A/C Condenser | 30 | 1.0 |
| A/C Evaporator | 60 | 2.0 |
| A/C Receiver/drier | 30 | 1.0 |
| A/C Compressor | Drain and measure the oil from the old compressor (See Compressor Oil Drain Procedure) | |