Circuit/System Testing
WARNING: This page is about a different car, the 2010 Pontiac G5 and 2010 Chevrolet Cobalt. However, it is still accessible from the selected car via links, so may be relevant.
- Ignition OFF, disconnect the harness connector at the appropriate actuator.
- Ignition OFF, test for less than 10 ohms between the low reference circuit terminal 7 and ground.
- If greater than the specified range, test the low reference circuit for an open/high resistance.
- Ignition ON, test for 4.8-5.2 volts between the 5-volt reference circuit terminal 10 and ground.
- If less than the specified range, test the 5-volt reference circuit for a short to ground or an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- If greater than the specified range, test the 5-volt reference circuit for a short to voltage.
- Using a DVOM verify the voltage on the signal circuit is greater than 4.8 volts.
- If less than the specified range, test the signal circuit terminal 9 for a short to ground.
- Install a 3A fused jumper wire between the signal circuit terminal 9 and the low reference circuit terminal 10. Using a DVOM verify the voltage on the signal circuit is greater than 0.2 volts.
- If greater than the specified range, test the signal circuit for a short to voltage or an open/high resistance.
- Ignition OFF, test for less than 10 ohms between the control circuit terminal 6 and ground.
- If greater than the specified range, test the control circuit for a short to voltage or an open/high resistance.
- Ignition OFF, test for less than 10 ohms between the control circuit terminal 5 and ground.
- If greater than the specified range, test the control circuit for a short to voltage or an open/high resistance.
- Connect a test lamp between control circuit terminal 5 and control circuit terminal 6.
- Command the appropriate actuator door in both directions. The test lamp should turn ON and OFF when commanded in both directions.
- If the test lamp remains OFF during either of the commands, test for a short to ground on either control circuit. If the circuits test normal, replace the HVAC control module.
- If both circuits test normal, test or replace the actuator.