System Evacuation

WARNING: This page is about a different car, the 2011 Honda Insight and 2010 Honda Insight. However, it is still accessible from the selected car via links, so may be relevant.
CAUTION:
  • Air conditioning refrigerant or lubricant vapor can irritate your eyes, nose, or throat.
  • Be careful when connecting service equipment.
  • Do not breathe refrigerant or vapor.

Use only service equipment for refrigerant HFC-134a (R-134a).

NOTE:
  • If accidental system discharge occurs, ventilate the work area before resuming service.
  • Additional health and safety information may be obtained from the refrigerant and lubricant manufacturers.
  • Do not allow moisture to contaminate the A/C system oil. Moisture in the oil is difficult to remove, and it can damage the A/C compressor.
  • Using a compact electronic vacuum gauge may decrease the required evacuation time because you can measure actual moisture level with this tool.

A more efficient way to measure moisture removal is with a special tool called a compact electronic vacuum gauge, measuring vacuum levels in microns.

Connect the tool according to the manufacturers instructions, and allow the vacuum pump to run until the gauge reads 500 microns.

Shut off and isolate the vacuum pump, then observe the gauge reading:

  1. When an A/C system has been opened to the atmosphere, such as during installation or repair, it must be evacuated using an R-134a refrigerant recovery/recycling/charging station. If the system has been open for several days, the receiver/dryer should be replaced, and the system should be evacuated for several hours.
  2. Connect an R-134a refrigerant recovery/recycling/charging station (A) to the high-pressure service port (B) and the low-pressure service port (C), as shown, following the equipment manufacturer's instructions. Recover the refrigerant, if any, from the A/C system (see REFRIGERANT RECOVERY ).
    Fig 1: Identifying Refrigerant Recovery/Recycling/Charging Station
    G06431415Courtesy of AMERICAN HONDA MOTOR CO., INC.
  3. Evacuate the system. The vacuum pump should run for a minimum of 30 minutes to eliminate all moisture from the system. When the suction gauge reads -93.3 kPa (-700 mmHg, -27.55 inHg) for at least 30 minutes, close all valves, and turn off the vacuum pump.
  4. If the low-pressure does not reach more than 93.3 kPa (700 mmHg, 27.6 in.Hg) in 15 minutes, there is probably a leak in the system. Partially charge the system, and check for leaks (see REFRIGERANT LEAK CHECK ).