Noise Diagnosis - HVAC Module
WARNING: This page is about a different car, the 2007 Pontiac G5 Pursuit, 2007 Pontiac G5, and 2007 Chevrolet Cobalt. However, it is still accessible from the selected car via links, so may be relevant.
Noise Diagnosis - HVAC Module
| Step | Action | Yes | No |
| DEFINITION: Noise originating from the HVAC module. | |||
| 1 | Were you sent here from Symptoms or another diagnostic table? | Go to Step 2 | Go to Symptoms - HVAC Systems - Manual |
| 2 |
|
Go to Step 6 | Go to Step 3 |
| 3 | Is a tick/click, chirping, groaning, or scraping noise present, but decreases as blower motor speed is decreased? | Go to Noise Diagnosis - Blower Motor | Go to Step 4 |
| 4 | Is an air rush/whistle noise evident in all modes but not all temperature settings? | Go to Step 6 | Go to Step 5 |
| 5 | Is an air rush/whistle noise evident only in defrost or floor mode? | Go to Step 6 | Go to Step 6 |
| 6 | Remove the center air outlet duct. Air Outlet Duct Replacement - Center . Is the action complete? |
Go to Step 7 | - |
| 7 |
|
Go to Step 10 | Go to Step 8 |
| 8 | Inspect the mode and temperature doors and seals for warping or cracking. Are the doors in normal condition? |
Go to Step 10 | Go to Step 9 |
| 9 | Replace the appropriate door and/or seals. Is the repair complete? |
Go to Step 10 | - |
| 10 | Remove any obstructions or foreign material found. Install any components that were removed. Is the action complete? |
Go to Step 11 | - |
| 11 |
|
Go to Step 12 | - |
| 12 | Operate the system to verify the repair. Did you find and correct the condition? |
System OK | Go to Step 2 |