Circuit Description
The following DTCs are for the air temperature sensors located in the discharge air ducts:
- B0174 is for the upper left air temperature sensor.
- B0179 is for the lower left air temperature sensor.
- B0510 is for the upper right air temperature sensor.
- B0515 is for the lower right air temperature sensor.
Air temperature sensors allow the HVAC control module to monitor the temperature of the discharge air in the HVAC ducts. The module applies 5 volts to internal input resistors that are connected to the signal circuits of the air temperature sensors. The module provides ground to the air temperature sensors through the low reference circuit. The HVAC control module monitors the voltage drops across the air temperature sensors and uses the inputs for automatic control calculations. When the duct air temperatures are cold, the resistances of the sensors are high and the voltage signals are high. When the duct air temperatures are hot, the resistances of the sensors are low and the voltage signals are low. The HVAC control module converts the voltage values to count values where 1 V is approximately equal to 51 counts.