Circuit/System Testing
WARNING: This page is about a different car, the 2009 Saturn Vue. However, it is still accessible from the selected car via links, so may be relevant.
- Ignition OFF, disconnect the harness connector at the appropriate actuator.
- Ignition OFF, test for less than 10 ohms between the low reference circuit terminal 1 and ground.
- If greater than the specified range, test the low reference circuit for an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- Ignition ON, test for 4.8-5.2 volts between the 5-volt reference circuit terminal 3 and ground.
- If less than the specified range, test the 5-volt reference circuit for a short to ground or an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- If greater than the specified range, test the 5-volt reference circuit for a short to voltage. If the circuit tests normal, replace the HVAC control module.
- Verify the appropriate scan tool Door Position parameter is greater than 250 counts.
- If less than the specified range, test the signal circuit terminal 2 for a short to ground. If the circuit tests normal, replace the HVAC control module.
- Install a 3A fused jumper wire between the signal circuit terminal 2 and the low reference circuit terminal 1. Verify the appropriate scan tool Door Position parameter is less than 3 counts.
- If greater than the specified range, test the signal circuit for a short to voltage or an open/high resistance. If the circuit tests normal, replace the HVAC control module.
- Ignition OFF, test for less than 10 ohms between the control circuit terminal 4 and ground.
- If greater than the specified range, test the control circuit for a short to voltage or an open/high resistance. If circuit tests normal, replace the HVAC control module.
- Ignition OFF, test for less than 10 ohms between the control circuit terminal 5 and ground.
- If greater than the specified range, test the control circuit for a short to voltage or an open/high resistance. If circuit tests normal, replace the HVAC control module.
- Connect a test lamp between control circuit terminal 5 and control circuit terminal 4.
- Command the appropriate actuator door in both directions with a scan tool. The test lamp should turn ON and OFF when commanded in both directions.
- If the test lamp remains OFF during either of the commands, test for a short to ground on either control circuit. If the circuits test normal, replace the HVAC control module.
- If both circuits test normal, test or replace the actuator.