Blower Motor Malfunction - Auxiliary (VIN 6 excluding Envoy XUV)
WARNING: This page does not describe the selected car, but rather 6 other vehicles, including the 2004 Oldsmobile Bravada, 2004 GMC Envoy XUV, 2004 GMC Envoy XL, 2004 GMC Envoy, and 2004 Chevrolet TrailBlazer. However, it is still accessible from the selected car via links, so may be relevant.
Blower Motor Malfunction - Auxiliary (VIN 6 excluding Envoy XUV)
| Step | Action | Values | Yes | No |
|---|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: The auxiliary blower motor operates in at least one speed position from at least one auxiliary control. |
||||
| 1 | Did you perform the HVAC Diagnostic System Check? | - | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 |
|
- | Go to Step 6 | Go to Step 3 |
| 3 | Test the auxiliary HVAC enable control circuit of the front auxiliary blower motor switch for an open, short to voltage or short to ground. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 4 |
| 4 | Test the low reference circuit of the front auxiliary blower motor switch for an open. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 5 |
| 5 |
|
Rear 5.0 V Off-1.0 V Pos.1 2.0 V Pos.2 3.0 V Pos.3 4.0 V | Go to Step 16 | Go to Step 17 |
| 6 |
IMPORTANT:
Ensure that the front auxiliary blower control switch is in the REAR position during the remainder of this table in order to avoid misdiagnosis.
|
- | Go to Step 7 | Go to Step 16 |
| 7 |
|
- | Go to Step 8 | Go to Step 16 |
| 8 | Place the auxiliary blower motor switch in each speed position. Does the auxiliary blower motor operate at the desired speeds? |
- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 9 |
| 9 |
|
- | Go to Step 14 | Go to Step 10 |
| 10 | Test the battery positive voltage circuit of the auxiliary blower motor control processor for a high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 11 |
| 11 | Test the ground circuit of the auxiliary blower motor control processor for a high resistance. Refer to Circuit Testing
and Wiring Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 12 |
| 12 |
IMPORTANT:
Ensure that the auxiliary blower motor control processor and auxiliary HVAC control module connectors are connected during this step in order to avoid misdiagnosis.
|
13.0-1.5 V | Go to Step 15 | Go to Step 13 |
| 13 |
|
8-12.5 V | Go to Step 16 | Go to Step 15 |
| 14 | Inspect for poor connections at the harness connector of the auxiliary blower motor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 19 |
| 15 | Inspect for poor connections at the harness connector of the auxiliary blower motor control processor. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 20 |
| 16 | Inspect for poor connections at the harness connector of the auxiliary HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 21 |
| 17 | Inspect for poor connections at the harness connector of the front auxiliary blower motor switch. Refer to Testing for Intermittent Conditions and Poor Connections
and Connector Repairs
in Wiring Systems. Did you find and correct the condition? |
- | Go to Step 22 | Go to Step 18 |
| 18 | Replace the front auxiliary blower motor switch. Refer to Front Auxiliary Blower Motor Switch Replacement
. Did you complete the replacement? |
- | Go to Step 22 | - |
| 19 | Replace the auxiliary blower motor. Refer to Blower Motor Replacement - Auxiliary (Rear Auxiliary)
or Blower Motor Replacement - Auxiliary (Front Auxiliary)
in Heating, Ventilation and Air Conditioning. Did you complete the replacement? |
- | Go to Step 22 | - |
| 20 | Replace the auxiliary blower motor control processor. Refer to Blower Motor Processor Replacement - Auxiliary . Did you complete the replacement? |
- | Go to Step 22 | - |
| 21 |
IMPORTANT:
Perform the recalibration procedure for the auxiliary HVAC control module. Replace the auxiliary HVAC control module. Refer to HVAC Control Module Replacement - Auxiliary .Did you complete the replacement? |
- | Go to Step 22 | - |
| 22 | Operate the system in order to verify the repair. Did you correct the condition? |
- | System OK | Go to Step 2 |