Refrigerant, Filling In Reservoir
-- Connect the cylinder with fresh refrigerant R1234yf to the service coupling on the low pressure side on the A/C Service Station. Refer to the A/C Service Station Owner's Manual.
-- Perform a gas analysis for the refrigerant to be filled (from the cylinder) using the A/C Service Station. Refer to REFRIGERANT GAS ANALYSIS, PERFORMING .
- Perform the procedure as described in the A/C Service Station Owner's Manual. Refer to A/C Service Station Owner's Manual.
There is a risk of explosion due to overfilling refrigerant cylinders.
Refrigerant can expand and the refrigerant cylinder can explode due to overfilling.
- Use a refrigerant cylinder with a safety valve.
- Never exceed the permitted capacity of the refrigerant cylinder.
Depending on the version of the A/C Service Station and the work procedures to be performed, there must be a certain minimum amount of refrigerant, refrigerant oil and UV-leak detection additive in the respective reservoirs on the A/C Service Station. Refer to the A/C Service Station Owner's Manual.