LEMON Manuals: Even more car manuals for everyone
Home >> Audi >> 2020 >> SQ8 Premium Plus >> Repair and Diagnosis >> External Pages >> Different car >> Section 211 (Air Conditioning (Refrigerant R1234YF Servicing) (Refrigerant Circuit)) >> 87 Air Conditioning >> Working With A/C Service Station >> Refrigerant Circuit, Evacuating >> Notes

Refrigerant Circuit, Evacuating: Notes

WARNING: This page is about a different car, the 2024 Audi SQ7, 2024 Audi Q7, 2023 Audi SQ7, and 2023 Audi Q7. However, it is still accessible from the selected car via links, so may be relevant.

The refrigerant circuit must be evacuated before it is filled with refrigerant (vacuum). Moisture is also extracted by this from the circuit.

Leaks may be found when evacuating the refrigerant circuit. Refer to LEAKS, FINDING .

CAUTION:

Risk of damaging the A/C compressor by the refrigerant circuit vacuum.

- Never start the engine with vacuum in the refrigerant circuit.

Evacuating:

-- On vehicles with a high-voltage system, switch off (deactivate) the "auxiliary climate control" function. Refer to the Owner's Manual and Infotainment/MMI Operating Manual.

-- Switch off the ignition.

-- Connect the A/C Service Station to the power supply.

Additionally on vehicles with electric operated valves in the refrigerant circuit, which cannot be opened without power:

NOTE:

For vehicles with a high-voltage system and additional A/C system functions (heat pump operation" or "cooling the high-voltage battery") valves may be installed in the refrigerant circuit that cannot be opened without current. These valves are opened and closed for example via a step motor and after switching off the ignition are no longer activated. To completely discharge, correctly evacuate and charge the refrigerant circuit, no sections may be closed. Therefore these valves must be opened before performing this work. Refer to Refrigerant Circuit (vehicle-specific service information) and Use the Vehicle Diagnostic Tester in the "Guided Fault Finding" function.

The check valves in the refrigerant circuit in the flow direction have a specified residual pressure (approximately 0.1 bar (1.45 psi) or 100 mbar (1.45 psi)). So that the refrigerant circuit can be completely evacuated (residual pressure less than 5 mbar (0.07 psi)) all electrically activated valves must be opened.

-- Open the electrically activated valves (not open without current) using the in the "Guided Fault Finding" function.

All Vehicles

-- Start the A/C Service Station according to its operating instructions. Refer to the A/C Service Station Operating Instructions.

-- Remove the closure caps from the refrigerant circuit service connections (refer to the vehicle-specific refrigerant circuit. Refer to Refrigerant Circuit (vehicle-specific service information).

-- Check the refrigerant circuit service connections for debris and corrosion and if necessary clean.

NOTE:

Dirt or a rough surface on the service connections due to corrosion can cause seal damage, which can then cause premature failure of the quick-release couplings.

-- Connect the A/C Service Station to the refrigerant circuit. Refer to A/C SERVICE STATION ON REFRIGERANT CIRCUIT, CONNECTING .

-- Switch on the A/C Service Station, evacuate the refrigerant and perform a pressure test (vacuum pump on for approximately 10 minutes to remove air, remaining refrigerant and moisture and 20 minute pressure/pressure increase test).

NOTE:

The vacuum at the end of the evacuation process must be less than 5 mbar (0.07 psi) absolute pressure (running vacuum pump of the A/C Service Station). If during the evacuation process the refrigerant circuit pressure is not smaller than 5 mbar (0.07 psi), this may have various causes: For example, a leak in the refrigerant circuit or in the connection to the A/C Service Station, the time set for the evacuation process is too short, the vacuum pump for the A/C Service Station does not generate the required amount of vacuum, or the vacuum sensor on the A/C service station is not calibrated correctly. Refer to the A/C Service Station Owner's Manual.

With an ambient pressure of 980 mbar (14.21 psi), for example, an absolute pressure of 5 mbar (0.07 psi) equates to a vacuum of 975 mbar (14.14 psi).

At the end of the vacuum/pressure increase test the refrigerant circuit pressure must not be higher than 20 mbar (0.29 psi) absolute pressure. If the refrigerant circuit pressure during the vacuum/pressure increase test is greater than 20 mbar (0.29 psi), the vacuum pump is switched on and the procedure begins again. Refer to the A/C Service Station Operating Instructions. If the procedure is repeated for a second time and the refrigerant circuit pressure still does not stay under 20 mbar (0.29 psi), this may have various causes. For example, a leak in the refrigerant circuit, a leak in the connection from the refrigerant circuit to the A/C Service Station or in the A/C Service Station itself can make the time for the evacuation process too short and the time for the vacuum/pressure increase test too long.

If it is suspected that a leak in the refrigerant circuit is present if necessary switch off the A/C Service Station and let it sit as long as possible (for example one hour to check for leaks in the refrigerant circuit). Refer to the A/C Service Station Owner's Manual.

Depending on the version of the A/C Service Station, the refrigerant circuit pressure is immediately displayed; however, it is also possible that only when the vacuum pump is running is the current pressure shown. Refer to the A/C Service Station Owner's Manual. If the A/C Service Station only displays the ambient pressure, then the refrigerant circuit pressure display depends on the ambient pressure when activated (if the ambient pressure is 980 mbar (14.21 psi), a vacuum of 975 mbar (14.14 psi) equates to a residual pressure of 5 mbar (0.07 psi) absolute pressure).

If the refrigerant circuit was opened, a small amount of moisture may have entered the refrigerant circuit. If this is the case, evacuate the refrigerant circuit for at least 30 minutes (refrigerant circuit pressure less than 20 mbar (0.29 psi) before filling).

If refrigerant was extracted (to check the capacity) and the refrigerant circuit is only evacuated to fill it again (the refrigerant circuit was not opened and has no leaks) it is enough to evacuate the refrigerant circuit for five minutes and no time or only a short amount of time (for example one minute) is needed adjust the vacuum/pressure increase test (no air and no moisture has entered the refrigerant circuit).

Depending on the quantity of refrigerant oil in the refrigerant circuit, the age and the mileage of the vehicle, the design of the refrigerant circuit etc., it is also possible that, on a leak-free refrigerant circuit, the specified absolute pressure in the refrigerant circuit rises over the specified 20 mbar (0.29 psi) during the vacuum test because of the refrigerant (and possibly even moisture) that has evaporated from the refrigerant oil. If this is the case, repeat the procedure again if necessary and/or adjust the pre-set times accordingly.

If the vacuum reading does not change (and the pressure remains smaller than 20 mbar (0.29 psi)) the system does not have leaks and can be filled.

NOTE:

Depending on the version of the A/C Service Station the current refrigerant circuit pressure is constant or is displayed after switching off for example the "Evacuate" function. Refer to the A/C Service Station Owner's Manual.

Due to the high evacuation temperature, it may be that the refrigerant evaporating from the refrigerant oil is increasing the refrigerant circuit pressure to 20 to 40 mbar (0.29 to 0.58 psi) (absolute pressure) during the vacuum test. This does not indicate a leak in the refrigerant circuit but depending on the version of the A/C Service Station can lead to a displayed malfunction. If necessary evacuate the refrigerant circuit again and monitor the vacuum indicator over a longer time, once the vacuum is maintained and it is ensured that there are no leaks in the refrigerant circuit, the system may be filled.

-- Charge the refrigerant circuit using the A/C Service Station. Refer to REFRIGERANT CIRCUIT, CHARGING .

If the vacuum is not maintained or if a sufficient vacuum cannot be generated, perform the following:

-- If there is any doubt as to whether or not the refrigerant circuit has leaks, evacuate again and monitor the vacuum indicator for a longer period of time. Only when the vacuum is maintained can the refrigerant circuit be charged.

-- It can only be filled once it is ensured that the refrigerant circuit does not have leaks. Refer to REFRIGERANT CIRCUIT, CHARGING .